Doc. No.:
560001 EG
Page:10
Ed.1" 08-2014
From ser. no.:
dor
When the time set on parameter
d8d
is expired, the alarm
dor
appear on the display, following from buzzer signaling and the red
light on blinking , (premium model only).
The alarm disappear when the door is closed.
The buzzer is off pressing the icon on display.
If the alarm is On with the door closed, this is due to :
- door not aligned
- control panel not aligned
- sensor broken
The calibration of infrared sensor is of 9 mm: over this distance
the sensor not more close the contact and the alarm will be al-
ways present.
0
0
EE
0
EF
When one of the other alarms apper on the display , check the
parameter list.
If the parameters setted are not kept in memory replace the
instrument.
EPROM ALARM
SERVICE ALARMS AND SIGNALLING
HI LO
TEMPERATURE ALARM
TEMPERATURE ALARM
"SER"
SEr
The icon light up and audible alarm sound when the compartement
temperature exceeds the set maximun value. The alarm ceases
when the temperature returns to Set point.
A Parameter
AL
and
AH
determine the threshold of alarm of hight
or lower temperature.
Another parameter as
Ad
determine the delay of alarm .
When the temperature return to set point, and the icon stay again
ON , press the button
PRG
or
directly on icon.
When the temperature of condenser is over of delta parameter
AC
with a delay time to
Acd
, the alarm “
SEr
” appears on the display
and the compressor if
stopped.
The alarm can be resetted pressing togheter the buttons
PRG
and
UP
and the delay
Acd
will be re setted. The compressor will
be ON only if the temperature reaches the value of AC-AE and the
time of value ( C1 ( compressor delay at power on) will expired. If
the alarm “
Ser
” appears again check if the condenser fan works or
not.
DOOR OPEN
Содержание Premium
Страница 37: ...Doc No 560001 EG Page 37 Ed 1 08 2014 From ser no E N G L I S H NOTE ...
Страница 38: ......