Page 98 KSSSI116
PU
, Indoor unit. (Capacitor Charge Malfunction) {Delayed}
Indoor
Heating
LED, flash
17
times.
Yellow-D5 LED
, Outdoor unit
Off
.
Orange-D6 LED
, Outdoor unit.
On
.
Green-D16 LED
, Outdoor unit
Off
.
Red-D30 LED
, Outdoor unit
On
.
# Check the
continuity
of the connecting wires from the outdoor PCB to the Reactor, as listed
below.
Solder point (Orange wire) on outdoor PCB to (Orange wire) terminal point on Reactor.
Solder point (White wire) on outdoor PCB to (White wire) terminal point on Reactor.
Check the continuity of the reactor. If open circuit, change it.
Terminal points of Reactor.
Solder points of Reactor on outdoor PCB.
Resistance reading of Reactor.
Содержание KSV26HRC
Страница 10: ...Page 10 KSSSI116 Electrostatic Discharge ...
Страница 11: ...Page 11 KSSSI116 ...
Страница 12: ...Page 12 KSSSI116 ...
Страница 30: ...Page 30 KSSSI116 KSV26CRC KSV26HRC Outdoor Unit mm KSV35CRC KSV35HRC Outdoor Unit mm ...
Страница 31: ...Page 31 KSSSI116 Dimensions KSV53HRC Indoor Unit mm ...
Страница 32: ...Page 32 KSSSI116 KSV53HRC Outdoor Unit Unit mm ...
Страница 34: ...Page 34 KSSSI116 Outdoor Unit KSV62HRC Unit mm KSV70CRC KSV70HRC KSV80HRC Unit mm ...
Страница 110: ...Page 110 KSSSI116 Wiring Diagrams KSV26 35 53CRC HRC Indoor ...
Страница 111: ...Page 111 KSSSI116 KSV62 70 80CRC HRC Indoor ...
Страница 112: ...Page 112 KSSSI116 KSV26 35CRC Outdoor ...
Страница 113: ...Page 113 KSSSI116 KSV26 35HRC Outdoor ...
Страница 114: ...Page 114 KSSSI116 KSV53 62HRC Outdoor ...
Страница 115: ...Page 115 KSSSI116 KSV70CRC Outdoor ...
Страница 116: ...Page 116 KSSSI116 KSV70 80HRC Outdoor ...
Страница 129: ...Page 129 KSSSI116 Remove the two screws supporting the front side panel Then push down remove Front Side Panel ...
Страница 133: ...Page 133 KSSSI116 ...