Page 88 KSSSI116
Diagnostic Display Mode Description:
Built into the software for models: KSV62, 70 & 80HRC are two different diagnostic methods:
(Fault Codes & Condition Codes) that can be used to help diagnose various faults.
These two diagnostic types are described in the following pages.
Note:
Where there is referral to (
Delayed
)
# This indicates a time delay before the fault code in question is displayed.
Note:
Where there is a referral to (
Remote Control Access – 4
)
# This indicates the need to use the remote controller to view the relevant fault code.
This is achieved by pressing the “Light” button 4 times within three seconds.
Note:
Where there is a referral to (
Remote Control Access – 5
)
# This indicates the need to use the remote controller to initiate a selected “Test State”.
This is achieved by pressing the “Light” button 5 times within three seconds.
Note:
Where there is a referral to (
DRED
)
# This indicates the unit in question is fitted with a “Demand Response Electrical Device” that
enables the compressor to operate at various capacities (75% of total capacity, 50% of total
capacity & compressor off).
Note:
The DRED device is provided & controlled by the local electrical authorities help control
peak demand periods.
Fault Code Descriptions:
E4
, Indoor Unit. (Compressor Discharge High Temperature Protection)
Indoor
Standby
LED, flash
4
times. {Delayed}
Yellow-D5 LED
, Outdoor unit
On
.
Orange-D6 LED
, Outdoor unit.
Off
.
Green-D16 LED
, Outdoor unit
On
.
Red-D30 LED
, Outdoor unit
Flashing
.
# Check the outdoor coil for airflow obstructions.
# Check the outdoor fan motor for correct operation.
E5
, Indoor Unit. (AC Over-Current Protection)
Indoor
Standby
LED, flash
5
times.
Yellow-D5 LED
, Outdoor unit
Off
.
Orange-D6 LED
, Outdoor unit.
On
.
Green-D16 LED
, Outdoor unit
Flashing
.
Red-D30 LED
, Outdoor unit
Off
.
# While the unit is in operation, check the maximum current draw. If it’s above the maximum
current rating illustrated on the outdoor rating plate, check operation of the compressor.
Содержание KSV26HRC
Страница 10: ...Page 10 KSSSI116 Electrostatic Discharge ...
Страница 11: ...Page 11 KSSSI116 ...
Страница 12: ...Page 12 KSSSI116 ...
Страница 30: ...Page 30 KSSSI116 KSV26CRC KSV26HRC Outdoor Unit mm KSV35CRC KSV35HRC Outdoor Unit mm ...
Страница 31: ...Page 31 KSSSI116 Dimensions KSV53HRC Indoor Unit mm ...
Страница 32: ...Page 32 KSSSI116 KSV53HRC Outdoor Unit Unit mm ...
Страница 34: ...Page 34 KSSSI116 Outdoor Unit KSV62HRC Unit mm KSV70CRC KSV70HRC KSV80HRC Unit mm ...
Страница 110: ...Page 110 KSSSI116 Wiring Diagrams KSV26 35 53CRC HRC Indoor ...
Страница 111: ...Page 111 KSSSI116 KSV62 70 80CRC HRC Indoor ...
Страница 112: ...Page 112 KSSSI116 KSV26 35CRC Outdoor ...
Страница 113: ...Page 113 KSSSI116 KSV26 35HRC Outdoor ...
Страница 114: ...Page 114 KSSSI116 KSV53 62HRC Outdoor ...
Страница 115: ...Page 115 KSSSI116 KSV70CRC Outdoor ...
Страница 116: ...Page 116 KSSSI116 KSV70 80HRC Outdoor ...
Страница 129: ...Page 129 KSSSI116 Remove the two screws supporting the front side panel Then push down remove Front Side Panel ...
Страница 133: ...Page 133 KSSSI116 ...