19
ENGLISH
3.7
Water-pump drainage
The maximum lifting height is 750mm.
Fig.24
3.8
Drainage pipe installation
1.
Installation principle
• Ensure at least 1/100 slope of the
drainage pipe.
• Adopt suitable pipe diameter
• Adopt nearby condensate water
discharge.
• Before installing condensate water
pipeline, determine its route and
elevation to avoid intersection with
other pipelines and ensure slope is
straight.
• In general, the supporter gap of the
drainage pipe horizontal pipe and
vertical pipe is respectively 1m~1.5m
and 1.5m~2.0m.
Fig.25
2.
Drainage pipe selection
• The drainage pipe diameter shall not
small than the drain hose of indoor unit.
• According to the water owrate and
drainage pipe slope to choose the
suitable pipe, the water owrate is
decided by the capacity of indoor unit.
Capacity(Btu/h)
Water owrate(l/h)
9000
2
12000
2.4
18000
4
• According to the above table to
calculate the total water owrate for the
conuence pipe selection.
• The horizontal pipe layout should avoid
converse ow or bad ow(Fig 26):
Fig.26
<200mm
1-1.5M
<750mm
Lean over 1/50
Pump-pipe clasp
(the ttings)
Too long distance
Gas bag
Drainage pipe
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drainage pipe
Drain tee
Drain tee