in confined spaces shall be avoided. The 

area around the workspace shall be sec-

tioned off. Ensure that the conditions within 

the area have been made safe by control 

of flammable material.

2.  Checking for presence of refrigerant:

  The area shall be checked with an appro-

priate refrigerant detector prior to and 

during work, to ensure the technician is 

aware of potentially toxic or flammable 

atmospheres. Ensure that the leak detec-

tion equipment being used is suitable for 

use with all applicable refrigerants, i.e.non-

sparking, adequately sealed or intrinsically 

safe

3.  Presence of fire extinguisher:

  If any hot work is to be conducted on the 

refrigeration equipment or any associated 

parts, appropriate fire extinguishing equip-

ment shall be available to hand. Have a 

dry powder or CO2 fire extinguisher adja-

cent to the charging area.

4.  No ignition sources:

  No person carrying out work in relation 

to a refrigeration system which involves 

exposing any pipe work shall use any 

sources of ignition in such a manner that 

it may lead to the risk of fire or explosion. 

All possible ignition sources, including 

cigarette smoking, should be kept suffi-

ciently far away from the site of installation, 

repairing, removing and disposal, during 

which refrigerant can possibly be released 

to the surrounding space.

  Prior to work taking place, the area around 

the equipment is to be surveyed to make 

sure that there are no flammable hazards 

or ignition risks.

  ‘No Smoking’ signs shall be displayed.

5.  Ventilated Area(open the door and win-

dow):

  Ensure that the area is in the open or that 

it is adequately ventilated before break-

ing into the system or conducting any hot 

work. A degree of ventilation shall continue 

during the period that the work is carried 

out. The ventilation should safely disperse 

any released refrigerant and preferably 

expel it externally into the atmosphere.

6.  Checks to the refrigeration equipment:

  Where electrical components are being 

changed, they shall be fit for the purpose 

and to the correct specification. At all 

times the manufacturer’s maintenance and 

service guidelines shall be followed. If in 

doubt, consult the manufacturer’s technical 

department for assistance. The following 

checks shall be applied to installations 

using flammable refrigerants:

•  The charge size is in accordance with the 

room size within which the refrigerant con-

taining parts are installed.

•  The ventilation machinery and outlets 

are operating adequately and are not 

obstructed.

•  If an indirect refrigerating circuit is being 

used, the secondary circuit shall be 

checked for the presence of refrigerant.

•  Refrigeration pipe or components are 

installed in a position where they are 

unlikely to be exposed to any substance 

which may corrode refrigerant containing 

components, unless the components are 

constructed of materials which are inher-

ently resistant to being corroded or are 

suitably protected against being so cor-

roded.

7.  Checks to electrical devices:

  Repair and maintenance to electrical com-

ponents shall include initial safety checks 

and component inspection procedures. If 

a fault exists that could compromise safety, 

then no electrical supply shall be con-

nected to the circuit until it is satisfactorily 

dealt with. If the fault cannot be corrected 

immediately but it is necessary to continue 

operation, an adequate temporary solution 

shall be used. This shall be reported to the 

owner of the equipment so all parties are 

advised.

Initial safety checks shall include:

•  That capacitors are discharged: this shall 

be done in a safe manner to avoid pos-

sibility of sparking. 

•  That no live electrical components and 

wiring are exposed while charging, recov-

ering or purging the system.

•  Keep continuity of earthing.

Inspection of Cable

Check the cable for wear, corrosion, overvolt-

age, vibration and check if there are sharp

edges and other adverse effects in the sur-

rounding environment. During the inspection,

the impact of aging or the continuous vibra-

tion of the compressor and the fan on it

should be taken into consideration

Leakage check of R290 refrigeran

Note:

 Check the leakage of the refrigerant 

in an environment where there is no poten-

tial ignition source. No halogen probe (or 

any other detector that uses an open flame) 

Содержание EACM-09 HR/N6

Страница 1: ...USER S MANUAL EACM 09 HR N6 EACM 12 HR N6 ...

Страница 2: ...able EACM 09 HR N6 EACM 12 HR N6 WE THINK ABOUT YOU Thank you for purchasing an Electrolux appliance You have chosen a product backed by decades of professional experience and innovations Unique and stylish it was created with care for you Therefore whenever you use it you can be sure that the results will always be excellent Welcome to Electrolux Content Safety information 3 Parts Description 4 C...

Страница 3: ... may cause harm or damage to people properties etc The seriousness is classified by the following indications WARNING This symbol indicates the possibility of death or serious injury CAUTION This symbol indicates the possibility of injury or damage to properties WARNING This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabiliti...

Страница 4: ...k fire or personal injury 1 The plug must be plugged into an outlet that is properly installed and grounded 2 Do not use an extension cord or plug adaptor with this unit CAUTION Don t apply the cold air to the body for a long time It will deteriorate your physical conditions and cause health problems Don t block air inlet or air outlet otherwise the cooling heating capacity will be weakened even c...

Страница 5: ...rol Panel TEMP indicator TEMP indicator In cooling or heating mode when or button is pressed the setting temperature is displayed and be adjusted 1 In auto cool and heat mode TEMP indica tor display is setting temperature 2 In dry and fan mode TEMP indicator dis play is room temperature Function buttons 1 button Press this button to make the unit run or stop 2 button a The running time of the unit...

Страница 6: ...G Failure to follow the below precaution could result in electrical shock fire explosion or personal injury 1 The plug must be plugged into an individual socket that is properly installed and grounded 2 Do not use an extension cord or plug adaptor with this unit Before starting the unit 1 Select a suitable location make sure the unit is near to an electrical outlet 2 Install the flexible exhaust h...

Страница 7: ...se it 2 No automatic wind sweep function models air louver minimum opening angle from air louver closed state breaking up 5 grid air louver opening angle can not be less than the minimum open angle when use it Unpacking Inspection Open the box and check unit in area with good ventilation open the door and win dow and without ignition source Note Operators are required to wear anti static devices I...

Страница 8: ...m The space shall not be less than usable space i2m2 in the specification The unit shall be installed at a well ventilated place Check the surrounding environment of installation site R290 shall not be installed in the enclosed reserved space of a build ing Installation Guide of customer The customer should have a qualified power supply coincident with that printed on the tag of the air conditione...

Страница 9: ... Screw A window slide kit Wall exhaust adaptor Adaptor B round mouth 2 Attach the window slider kit to the window sash Adjust the length of the Window Slider Kit Loose the screw A to adjust the length of the Window Slider Kit then tight the screw when the length is suitable Note the length of the Window Slider Kit is 67 5cm to 120cm Screw B 3 Carefully lower the window Secure the vent panel in pla...

Страница 10: ...efficiency As the following fig Shows Do not Yes Without installation If the unit does not have the window slider kit and wall exhaust and the Adaptor В is like this as shown in Fig H You can open the window slightly and position as shown in Fig I Fig H Fig I Water drainage During dehumidifying mode remove the upper drain plug from the back of the unit Attach the drain hose to the hole Place the o...

Страница 11: ...ouring water directly over any of the surface areas as this will cause deterioration of electrical components and wiring insulation Clean the unit When the unit is contaminated clean it gently with a wrung towel using tepid water below 40 C 104 F Clean the Air Filter 1 Remove the air filter Take out the upper air filter and the lower air filter Note There are two types about the low air intake gri...

Страница 12: ...itioner with R290 refrigerant and maintain the air conditioner in strictly accordance with manufacturer s requirements The chapter is mainly focused on special maintenance requirements for appliance with R290 refrigerant Ask repairer to read after sales technical service handbook for detailed information Qualification requirements of maintenance personnel 1 Special training additional to usual ref...

Страница 13: ... correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant con taining parts are installed The ventilation mach...

Страница 14: ... to reach the working pressure under the vacuum state then the oxygen free nitrogen is emitted to the atmosphere and in the end vacuumize the system Repeat this process until all refrigerants in the system is cleared After the final charging of the anaerobic nitrogen discharge the gas into the atmosphere pres sure and then the system can be welded This operation is necessary for welding the pipeli...

Страница 15: ... and they should be in a good condition If possible empty tanks should be evacu ated and maintained at room temperature before use 3 The recovery equipment should be kept in a good working condition and equipped with equipment operating instructions for easy access The equipment should be suitable for the recovery of R290 refriger ants Besides there should be a quali fied weighting apparatus which...

Страница 16: ...ay be considered as expendable supplies or which are made of glass The warranty is void if the defect is caused by damage ensuing by misuse poor maintenance for example a failure occurred due to ingress of foreign objects or liquids or if changes or repairs were performed by persons not authorized by the Manufacturer For the correct use of the product the user must strictly follow all included in ...

Страница 17: ...in technical and typing errors Changes to technical characteristics and assortment are subject to change without notice Mistakes and typing errors may be permitted in texts and numeric notations Product design and technical data may vary from the one pictured on the packaging Please refer to a sales consultant for more detailed information ...

Страница 18: ......

Страница 19: ...Seller Seal Date of sale Model Product Details populated upon sale Serial number ...

Страница 20: ...via Estonia and CIS countries only Electrolux is a registered trademark used under license from AB Electrolux publ This manual may contain technical and typing errors Changes to technical characteristics and assortment are subject to change without notice ...

Отзывы: