Operational Tips
Outlet Temperature Setting
The inside circuit board contains two screwdriver switches marked Ø through 7. Adjust them to select the
desired set point for your application.
EX: Ideal set point = 86°
Mode Dial would be set to #4
Warm Air Dial would be set to #0
NOTE: MODE DIAL setting # 7 is not applicable to this product
Mode Dial Temperature Range Options
MODE
DIAL
WARM
AIR
DIAL
0
1
2
3
4
5
6
7
0
‐
10
14
38
62
86
110
134
MUA
II
1
‐
7
17
41
65
89
113
137
2
‐
4
20
44
68
92
116
140
3
‐
1
23
47
71
95
119
140
4
2
26
50
74
98
122
140
5
5
29
53
77
101
125
140
6
8
32
56
80
104
128
140
7
11
35
59
83
107
131
140
Checkout and Calibration
There is no field calibration or adjustments.
Total element turn on can be accomplished by jumpering system “R” (24 volts) to “W” internal terminal. In
essence, this bypasses the temperature modulation function and causes the element to be full on.
However, see previous section “Summer or Cooling Disable”.