General
This is a packaged electric element section, using finned rod elements, with a remote sensing control package
for modulating the electric elements.
The typical installation arrangement is shown in FIGURE 1.
The element power is standard 240-volt, single phase. Control is simply supplying the two control wires
with 24 volts to turn the unit on.
Caution:
The control contact mechanism for supplying 24 volts to the yellow and black wires must
have interlocking devices to assure airflow and the proper opening of any motorized dampers. This
unit depends upon an external blower or air moving device providing minimal airflow across the
electric elements before “turning the unit on”. Minimum airflow relates to temperature rise needs or
design, Table 2 – CFM Chart, provides these CFM numbers.
FIGURE 1
Table 1 Electrical Requirements
Model kW*
Btu/h
Nameplate
Current*
Duct Collar
EM-WX02-240-1-08 2.5 8,500
10.5
8”
EM-WX05-240-1-08 5 17,000 21
8”
EM-WX10-240-1-10 10 34,000
42
10”
* Based upon full turn-on or 100% modulation.
Table 2 CFM Chart
Temperature Rise Needed
80
70
60
50
40
30
Model number
Watts
CFM
CFM
CFM
CFM
CFM
CFM
EM-WX02-240-1-08
2500
99
113
132
158
198
263
EM-WX05-240-1-08
5000
198
226
263
316
395
527
EM-WX10-240-1-10
10000
395
452
527
632
790
1054