Electro Industries/GaugeTech
Doc #: E107-7-06-121
5-21
5.17: Remote Communication
5.17: Remote Communication—
—RS-232
RS-232
n
EIG recommends using RS-485 wiring with a Modem Manager. See section 5.13.
n
For RS-232 communication, use Port 1. Set the selector switch under the port to RS-232 (Fig. 5.3).
n
Use an RS-232 serial extension cable connected to the 9-pin female serial port of the Nexus
Monitor’s Port 1. Program this port for Modbus ASCII. See the
Nexus Communicator User Manual
for details.
n
The link using RS-232 is capable for up to 50 feet (1219 meters).
n
You
must
use a Null Modem or Null Cable between the Nexus Monitor and the remote modem
when using RS-232. A Null Modem enables two DCE devices to communicate. The figure below
details how a null modem reconfigures the RS-232 pins.
Note: Connecting the Nexus Monitor to a
modem via RS-485 protocol with EIG’s Modem Manager converter eliminates the need for a
Null Modem; see section 5.13.
n
The remote modem must be programmed for auto-answer and set at a fixed baud rate of 9600 with
no Flow Control. See section 5.19 and the
Nexus Communicator User Manual
for further details.
1
6
5
4
7
20
8
3
2
1
2
3
4
5
6
7
8
20
Pins at Null Modem Female End
Pins at Null Modem Male End
Figure 5.19: Standard Null Modem Configuration
5.18: Remote Communication
5.18: Remote Communication—
—RS-485
RS-485
n
Use any Port on the Nexus. If you use Port 1, set the selector switch beneath the port to RS-485 (see
Figure 5.3). The link using RS-485 is capable for up to 4000 feet (1219 meters).
n
Use Nexus Communicator software to set the port’s baud rate to 9600 and enable Modbus ASCII
protocol. See the
Nexus Communicator User Manual
.
n
You
must
use an RS-485 to RS-232 converter and a NULL Modem. EIG recommends using its
Modem Manager
, a sophisticated RS-232/RS-485 converter that enables devices with different
baud rates to communicate. It also eliminates the need for a NULL modem (see section 5.12), and
automatically programs the modem to the proper configuration. Also, if the telephone lines are poor,
Modem Manager acts as a line buffer, making the communication more reliable.
Содержание Nexus 1250
Страница 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Страница 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Страница 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Страница 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Страница 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...