![Electro Industries/GaugeTech Nexus 1250 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1250/nexus-1250_installation-and-operation-manual_2379729018.webp)
e
Electro Industries/GaugeTech
Doc #: E107-7-06-121
2-2
n
Nexus 1250 Revenue Metering:
•
Delivers laboratory-grade 0.04% Watt-hour accuracy in a field-mounted device.
•
Auto-calibrates when there is a temperature change of more than 10 degrees centigrade.
•
Exceeds all ANSI C-12 and IEC 687 specifications.
•
Adjusts for transformer and line losses, using user-defined compensation factors.
•
Automatically logs time-of-use for up to eight programmable tariff registers.
•
Counts pulses and aggregates different loads.
n
Nexus 1250 Power Quality Monitoring:
•
Records up to 512 samples per cycle on an event.
•
Records sub-cycle transients on voltage or current readings.
•
Measures and records Harmonics to the 83rd order.
•
Offers inputs for neutral-to-ground voltage measurements.
•
Synchronizes with IRIG-B clock signal.
n
Nexus 1250 Memory, Communication and Control:
•
Up to 4 Meg NVRAM.
•
4 High Speed Communication Ports.
•
Multiple Protocols.
•
Built-in RTU functionality.
•
Built-in PLC functionality.
•
90msec High Speed Updates for Control.
Содержание Nexus 1250
Страница 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Страница 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Страница 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Страница 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Страница 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...