background image

INPUT & OUTPUTS CONNECTION EXAMPLE

DIGITAL INPUTS AND OUTPUTS CONNECTION

(only for the version PFA6C11-12)

S1 S2 S1 S2 S1 S2 A B

T

10 11 12

17

18

19

20

U1 U2 U3

N

I1

I2

I3

RS-485

AUX

AUX

VOLTAGE INPUT POWER

NO

C

NC

NO

C

NC

Max
27 Vdc
27 mA

(-)

(+)

230 Vac

FROM: 
- TRANSDUCER WITH CONTACT CLEAN
- GME
- STATE ON-OFF
- STATE ALARMS

R

e

l

a

y

R

e

l

a

y

Power

Supply

Digital Inputs

Supply voltage (external):

from 10 to 30 
Vdc

Current consumption:

from 2 to 10mA

Max. count frequency

10 or 100Hz

N.B. For gas meters a galvanic separation is 
needed per ATEX standards

Digital outputs (optocoupled NPN 
transistor type for DIN 43864)

Maximum applicable voltage:

27 Vdc

Maximum switchable current:

27 mA

S1 S2 S1 S2 S1 S2 A B

T

10 11 12

17

18

19

20

U1 U2 U3

N

I1

I2

I3

RS-485

AUX

AUX

VOLTAGE INPUT POWER

Es.
Input M8 Supervisor

1 2 C

C

3 4

(+)

(-)

(-) (+) (+)

Es. PLC

Out PLC

Common

Note n.1

3PH-3W-2CT 2 phases 3 wires, triangle
3PH-4W

3 phases 4 wires, Star

2PH-2W

2 phases 2 wires, biphase

1PH-2W

1 phase 2 wires, monophase

Note n.2

POWERS

Integration time of the average value (AVG) and peak value (MD) for 
power (from 1 to 60 minutes)

CURRENTS Integration time of the average value (AVG) and peak value (MD) for 

current (from 1 to 60 minutes)

Note n.3
Normal

Classic  Alarm  with  reference  to  a  fi xed  threshold  or  to  maximum  and 
minimum delay and applicable hysteresis. “AVG” parameter is not used. 

1-OF-3

Consider  also  the  2  following  registers  of  the  selected  one  in  “MEAS”  . 
Works on a fi xed max or min threshold with delay and applicable hysteresis. 
If one of the three register exceed the threshold the alarm goes on. “AVG” 
parameter is not used.

3-OF-3

Consider  also  the  2  following  registers  of  the  selected  one  in  “MEAS”. 
Works on a fi xed max or min threshold with delay and applicable hysteresis. 
When all the three register exceed the threshold the alarm goes on. “AVG” 
parameter is not used.

DERIV

“THRE”  parameter  becomes  a  %  value,  “AVG”  parameter  is  used.  The 
instant value applied to the alarm on “MEAS” is compared with its value 
mediated  obtained  on  the  basis  of  the  time  set  on  “AVG”.  When  the 
instantaneous value combined alarm differs in more (setting “Max”) or less 
(setting “MIN”) from the average value (“ AVG “) of the percentage set on 
“THRE” the alarm goes on. With delay and applicable hysteresis. 

UNBAL

Consider  also  the  2  following  registers  of  the  selected  one  in  “MEAS”.  
“THRE” parameter becomes a % value. Alarm goes on when one of the 
three register is different from the percentage set on “THRE” comply with 
the higher value of the three read register if “MAX” is set on “TYPE”, or 
comply with the lower value of the three register if “MIN” is set on “TYPE”
With delay and applicable hysteresis.

Note n.4
MAX

Alarm setting in excess compared with the established conditions.
With the exception of “UNBAL”.

MIN

Alarm setting in decrease compared with the established conditions. 
With the exception of “UNBAL”

Note n.5

MEAS

indicates which register (and thus measure) the alarm is related.
See table n.1 input register.

THRE

Alarm threshold in absolute value, with the exception made for “DERIV” 
and “UNBAL” in which the value inserted becomes a percentage.

Note n.6

AVG

Parameter to be used only in “DERIV” mode. Is the duration of the refe-
rence (in seconds) used to create a reference value for the istantaneous 
readings.

Note n.7
NORMAL

Physical output of the alarm excited during the duration of the alarm. It 
restores automatically

HOLD

Output remains excited until manual reset made via Modbus

PULSE-L

Output generate a 500ms impulse when the alarm goes on.

PULSE-S

Output generate a 100ms impulse when the alarm goes on.

Note n.8

PULSE

Enables exit function as impulsive

ALARM

Enables exit function as alarm

REMOTE

Enables function output via protocol Modbus

NO

Normally open

NC

Normally closed

Note n.9

P-IMP

Imported Active Power (Energy)

QL-IMP

Imported Reactive Inductive Power (Energy)

QC-IMP

Imported Reactive Capacitive Power (Energy)

S-IMP

Imported Apparent Power (Energy)

P-EXP

Exported Active Power (Energy)

QL-EXP

Exported Reactive Inductive Power (Energy)

QC-EXP

Exported Reactive Capacitive Power (Energy)

S-EXP

Exported Apparent Power (Energy)

Note n.10

YES

Referred to CT primary

NO

Referred to CT secondary

Note n.11
ALLARME 1

Alarm related to the physical output: DIGITAL OUT 1 (DO1, terminal 8)

ALLARME 2

Alarm related to the physical output: DIGITAL OUT 2 (DO2, terminal 9)

ALLARME 3

Only MODBUS alarm

ALLARME 4

Only MODBUS alarm

ALARM SET UP EXAMPLE

To ensure that the exit “DIGITAL OUT 1” remain excited for the alarm duration (latching) 
when average active power (MEAS 344) exceeds the value of 100 kW, hysteresis, 5% 
and latency of 5 seconds set the parameters such as table:

ALARM 1 / A

MODE (

note n.2)

Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL

NORMAL

TYPE (

note n.3)

MAX, MIN

MAX

MEAS (

note n.4)

Controlled measure. See table n.1 for register 
selection

344

THRE (

note n.4)

Threshold value

100000

ALARM 1 / B

HYST

1...100 (%)

5

DELAY

1...99 (seconds)

5

AVG (

note n.5)

1...99 (seconds)

1

OUT (

note n.6)

Normal, Hold, Pulse-L, Pulse-S

NORMAL

DIGITAL OUT 1

MODE

PULSE, ALARM, REMOTE

ALARM

POLARITY

NO, NC

NO

To ensure that the exit “DIGITAL OUT 2” remain excited for the alarm duration (latching) 
when average active power (MEAS 344) goes down the value of 90 kW, hysteresis, 5% 
and latency of 5 seconds set the parameters such as table:

ALARM 2 / A

MODE (

note n.2)

Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL

NORMAL

TYPE (

note n.3)

MAX, MIN

MIN

MEAS (

note n.4)

Controlled measure. See table n.1 for register 
selection

344

THRE (

note n.4)

Threshold value

90000

ALARM 2 / B

HYST

1...100 (%)

5

DELAY

1...99 (seconds)

5

AVG (

note n.5)

1...99 (seconds)

1

OUT (

note n.6)

Normal, Hold, Pulse-L, Pulse-S

NORMAL

DIGITAL OUT 2

MODE

PULSE, ALARM, REMOTE

ALARM

POLARITY

NO, NC

NO

C

10

1

11

2

12

AUX

IN/OUT

!

Common

12

11

10

DO2

DO1

DI (+)

20

19

DI (-)

+

19

-

20

AUX

IN/OUT

!

MESSAGE “CFG ERROR”

During the set up operation a “CFG ERROR” message could appear. This means 
that some wrong parameters are typed. To restore the factory default settings use the 
following procedure (RESTORE FACTORY SETTING):

CFG ERROR

RESTORE

FACTORY SETTINGS

YES

Once this procedure is done the meter is confi gured with its factory default settings. 
Stored data will remain after the restore operation.

Содержание Femto D4

Страница 1: ...ts returned as detective but found to be perfectly working by our laboratories will be charged a flat fee to account for checking and testing time irrespective of the warranty terms SAFETY This instrument was manufactured and tested in compliance with CEI EN 61010 1 CAT III 300V class 2 standards for operating voltages up to 300 VAC rms phase to neutral In order to maintain this condition and to en...

Страница 2: ...uency of U1N f Hz 220 Phase to Neutral Voltage RMS Amplitude U1N V 222 Phase to Neutral Voltage RMS Amplitude U2N V 224 Phase to Neutral Voltage RMS Amplitude U3N V 226 Phase to Phase Voltage RMS Amplitude U12 V 228 Phase to Phase Voltage RMS Amplitude U23 V 230 Phase to Phase Voltage RMS Amplitude U31 V 232 Phase Current RMS Amplitude I1 A 234 Phase Current RMS Amplitude I2 A 236 Phase Current RM...

Страница 3: ...HRE Alarm threshold in absolute value with the exception made for DERIV and UNBAL in which the value inserted becomes a percentage Note n 6 AVG Parameter to be used only in DERIV mode Is the duration of the refe rence in seconds used to create a reference value for the istantaneous readings Note n 7 NORMAL Physical output of the alarm excited during the duration of the alarm It restores automatica...

Страница 4: ...cted Disregard of this warning or of wiring diagram leads to major measurement errors VOLTAGE AND CURRENT CONNECTION S1 S2 S1 S2 S1 S2 A B T 10 11 12 17 18 19 20 U1 U2 U3 N I1 I2 I3 RS 485 AUX AUX VOLTAGE INPUT POWER L N FUSE 50mA T 230 240 V 10 Serial RS485 port A B T Subject to modification without notice Edition 2015 04 24 ENG0055 STAR 4W 4 WIRES 3PH 4W SINGLE PHASE 1PH 2W BI PHASE 2PH 2W TRIANG...

Отзывы: