DEVICE SETUP
OPERATING KEYS
Click
Change selected fi eld
value
Change selected fi eld value
Go to next fi eld
Click
2 sec
Go to next window
Back to initial entry fi eld
Exits setup
SETUP SEQUENCE
PAGE
PARAMETERS
VALUES AVAILABLE
DEFAULT
PASSWORD REQUEST
0000 ... 9999
0000
RS485
RS485 Address
1 ... 247
27
Rate
2400, 4800, 9600, 19200, 38400
38400
Data Bit
7 or 8
8
Parity
N = no parity, E =even parity, O = odd parity
N
Stop Bit
1 or 2
2
RS-485
ADDR 027
COM 38400-8-N-2
S.T.
100
NETWORK
Type
(note n.1)
3PH-3W-2CT, 3PH-4W, 2PH-2W, 1PH-2W
3PH-4W
Export
NO, YES
NO
CT
10000/1 or 5
5/5
VT
400000/300
1/1
NETWORK
TYPE 3PH-4W
EXPORT NO
CT 00005/5
VT 000001/001
AVG-MD TIME
(note n.2)
POWERS
1...60 (minutes)
15
CURRENTS
1...60 (minutes)
8
AVG-MD TIME
POWERS 15
CURRENTS 08
ALARM 1 / A
(
note n.11)
MODE (
note n.3)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
NORMAL
TYPE (
note n.4)
MAX, MIN
MIN
MEAS (
note n.5)
Controlled measure. See table n.1 for register
selection
200
THRE (
note n.5)
Threshold value
0
ALARM 1/A
MODE NORMAL
TYPE MIN
MEAS 200
THRE 000.00
ALARM 1 / B
HYST
1...100 (%)
1
DELAY
1...99 (seconds)
1
AVG (
note n.6)
1...99 (seconds)
1
OUT (
note n.7)
Normal, Hold, Pulse-L, Pulse-S
NORMAL
ALARM 1/B
HYST 01
DELAY 01 S/01 S
AVG 01
OUT NORMAL
ALARM 2 / A
(
note n.11)
MODE (
note n.3)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
NORMAL
TYPE (
note n.4)
MAX, MIN
MIN
MEAS (
note n.5)
Controlled measure. See table n.1 for register
selection
200
THRE (
note n.5)
Threshold value
0
ALARM 2 / B
HYST
1...100 (%)
1
DELAY
1...99 (seconds)
1
AVG (
note n.6)
1...99 (seconds)
1
OUT (
note n.7)
Normal, Hold, Pulse-L, Pulse-S
NORMAL
ALARM 3 / A
(
note n.11)
MODE (
note n.3)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
NORMAL
TYPE (
note n.4)
MAX, MIN
MIN
MEAS (
note n.5)
Controlled measure. See table n.1 for register
selection
200
THRE (
note n.5)
Threshold value
0
ALARM 3 / B
HYST
1...100 (%)
1
DELAY
1...99 (seconds)
1
AVG (
note n.6)
1...99 (seconds)
1
OUT (
note n.7)
Normal, Hold, Pulse-L, Pulse-S
NORMAL
ALARM 4 / A
(
note n.11)
MODE (
note n.3)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
NORMAL
TYPE (
note n.4)
MAX, MIN
MIN
MEAS (
note n.5)
Controlled measure. See table n.1 for register
selection
200
THRE (
note n.5)
Threshold value
0
ALARM 4 / B
HYST
1...100 (%)
1
DELAY
1...99 (seconds)
1
AVG (
note n.6)
1...99 (seconds)
1
OUT (
note n.7)
Normal, Hold, Pulse-L, Pulse-S
NORMAL
ENTERS INTO SET UP MODE
(Push together for 2 seconds)
TABLE n.1 (ModBus Registers for alarm confi guration)
REGISTER DESCRIPTION
SYMBOL
UNITS
200
Phase to Neutral Voltage, THD
THD U1N
[%]
202
Phase to Neutral Voltage, THD
THD U2N
[%]
204
Phase to Neutral Voltage, THD
THD U3N
[%]
206
Phase to Phase Voltage, THD
THD U12
[%]
208
Phase to Phase Voltage, THD
THD U23
[%]
210
Phase to Phase Voltage, THD
THD U31
[%]
212
Phase Current, THD
THD I1
[%]
214
Phase Current, THD
THD I2
[%]
216
Phase Current, THD
THD I3
[%]
218
Frequency of U1N
f
[Hz]
220
Phase to Neutral Voltage, RMS Amplitude
U1N
[V]
222
Phase to Neutral Voltage, RMS Amplitude
U2N
[V]
224
Phase to Neutral Voltage, RMS Amplitude
U3N
[V]
226
Phase to Phase Voltage, RMS Amplitude
U12
[V]
228
Phase to Phase Voltage, RMS Amplitude
U23
[V]
230
Phase to Phase Voltage, RMS Amplitude
U31
[V]
232
Phase Current, RMS Amplitude
I1
[A]
234
Phase Current, RMS Amplitude
I2
[A]
236
Phase Current, RMS Amplitude
I3
[A]
238
Neutral Current, RMS Amplitude
IN
[A]
240
Phase Active Power ( Imp/ Exp)
P1
[W]
242
Phase Active Power ( Imp/ Exp)
P2
[W]
244
Phase Active Power ( Imp/ Exp)
P3
[W]
246
Phase Reactive Power ( Imp/ Exp)
Q1
[var]
248
Phase Reactive Power ( Imp/ Exp)
Q2
[var]
250
Phase Reactive Power ( Imp/ Exp)
Q3
[var]
252
Phase Apparent Power
S1
[VA]
254
Phase Apparent Power
S2
[VA]
256
Phase Apparent Power
S3
[VA]
258
Phase Power Factor ( Imp/ Exp)
PF1
[-]
260
Phase Power Factor ( Imp/ Exp)
PF2
[-]
262
Phase Power Factor ( Imp/ Exp)
PF3
[-]
264
Phase to Neutral Voltage, Mean THD
THD Ul
[%]
266
Phase to Phase Voltage, Mean THD
THD UD
[%]
268
Phase Current, Mean THD
THD I
[%]
270
Phase to Neutral Voltage, Mean RMS Amplitude
Ul
[V]
272
Phase to Phase Voltage, Mean RMS Amplitude
UD
[V]
274
Three phase current, RMS Amplitude
I
[A]
276
Total active power ( Imp/ Exp)
PS
[W]
278
Total reactive power ( Imp/ Exp)
QS
[var]
280
Total apparent power
SS
[VA]
282
Total power factor ( Imp/ Exp)
PFS
[-]
332
Phase Current, RMS Amplitude, AVG
I1 AVG
[A]
334
Phase Current, RMS Amplitude, AVG
I2 AVG
[A]
336
Phase Current, RMS Amplitude, AVG
I3 AVG
[A]
344
Total imported active power, AVG
P Imp AVG
[W]
346
Total imported inductive power, AVG
Qind Imp AVG [var]
348
Total imported capacitive power, AVG
Qcap Imp AVG [var]
350
Total imported apparent power, AVG
S Imp AVG
[VA]
352
Total exported active power, AVG
P Exp AVG
[W]
354
Total exported inductive power, AVG
Qind Exp AVG [var]
356
Total exported capacitive power, AVG
Qcap Exp AVG [var]
358
Total exported apparent power, AVG
S Exp AVG
[VA]
376
External Pulse Counter, With Weight, Total counter
or Tariff T1
CNT1 S
384
External Pulse Counter, With Weight, Partial
Counter or Tariff T2
CNT1 P
EXIT SETUP
(push for 2 seconds)
DISPLAY
CONTRAST
20 - 45
28
DIGITAL OUT 1
(
note n.8)
MODE
PULSE, ALARM, REMOTE
PULSE
POLARITY
NO, NC
NO
DIGITAL OUT 1
MODE PULSE
POLATITY NO
PULSE OUT 1
MEAS (
note n.9)
P-IMP, QL-IMP, QC-IMP, S-IMP, P-EXP,
QL-EXP, QC-EXP, S-EXP
P-IMP
PRIMARY (
note n.10)
YES, NO
YES
WEIGHT
1...100000000 (Wh/100)
100000
WIDTH
50ms...1S
500
PULSE OUT 1
MEAS P-IMP
PRIMARY YES
WEIGHT 100.00k
WIDTH 0500
DIGITAL OUT 2
(
note n.8)
MODE
PULSE, ALARM, REMOTE
PULSE
POLARITY
NO, NC
NO
PULSE OUT 2
MEAS (
note n.9)
P-IMP, QL-IMP, QC-IMP, S-IMP, P-EXP,
QL-EXP, QC-EXP, S-EXP
QL-IMP
PRIMARY (
note n.10)
YES, NO
YES
WEIGHT
1...100000000 (Wh/100)
100000
WIDTH
50ms...1S
500
CLEAR TOTAL COUNTERS
NO, YES
NO
CLEAR PARTIAL COUNTERS
NO, YES
NO
CLEAR MIN-MAX
NO, YES
NO
CLEAR MAX DEMAND
NO, YES
NO
RESTORE FACTORY SETTINGS
NO, YES
NO
ENTER NEW PASSWORD
0000 ... 9999
0000