11-14
CONTROL SYSTEM
SM WNGDCI 1-E.1 GB
11.13
SW Parameters
11.13.1
Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in
heat mode (ICT):
ICTST Speed ICT to stop indoor fan
25
ICTVLSpeed
ICT to go down to very low speed
28
ICTLSpeed
ICT to start in very low speed
30
ICTHSpeed
ICT to start in increase speed from very low
32
ICTTSpeed
ICT to enable Turbo fan speed
40
Model Depended Parameters:
Parameter name
Wall Mounted Models
DCI 25
DCI 35
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C
40
40
MaxNLOADIF2C
53
53
MaxNLOADIF3C
120
120
MaxNLOADIF4C
127
127
MaxNLOADIF5C
127
127
Indoor Fan speeds
IFVLOWC
700
700
IFLOWC
800
800
IFMEDC
900
950
IFHIGHC
1050
1100
IFTURBOC
1150
1200
IFVLOWH
700
700
IFLOWH
800
850
IFMEDH
950
1000
IFHIGHH
1100
1150
IFTURBOH
1200
1250
Nominal Compressor Frequency
NomLoadC
40
62
NomLoadH
55
67
Parameter Name
Cassette Models
K 25
K 35
K 35S
K 50
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C
40
40
40
40
MaxNLOADIF2C
53
56
56
60
MaxNLOADIF3C
120
90
90
90
MaxNLOADIF4C
127
90
90
90
MaxNLOADIF5C
127
90
90
90
Nominal Compressor Frequency
NomLoadC
40
60
56
63
NomLoadH
55
69
73
80
CONTENTS
Содержание WNG 25 DCI Series
Страница 51: ...13 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM WNGDCI 1 E 1 GB 13 3 Indoor Unit N WNG 25 35 LCD DCI CONTENTS ...
Страница 53: ...13 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM WNGDCI 1 E 1 GB 13 5 Indoor Unit WNG 25 35 LED DCI CONTENTS ...
Страница 55: ...13 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM WNGDCI 1 E 1 GB 13 7 Indoor Unit WNG 25 35 LED DCI CONTENTS ...
Страница 57: ...13 9 EXPLODED VIEWS AND SPARE PARTS LISTS SM WNGDCI 1 E 1 GB 13 9 Outdoor Unit ONG 25 35 DCI new CONTENTS ...