11-13
CONTROL SYSTEM
SM WNGDCI 1-E.1 GB
11.12
Test Mode
11.12.1
Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode
l, Set point 16, Room temper
= Coo
=
ature = 27±1, Outdoor temperature = 35±1
Or
Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 16
Mode = Heat, Set point = 30
11.12.2
Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed Setting
Unit Setting
Low
Minimum Capacity Setting
High
Nominal Capacity Setting
Auto
Maximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.