Operation
The Thermecro digital controller is designed for use with the Themecro pool
interface valve to facilitate the harvesting of heat from the solar array in the
most efficient way possible.
The solar array water temperature and pool water temperature are
measured continuously.
When the solar array temperature is greater than the ‘set water temperature’
+ the ‘on differential temperature’ the controller will open the stainless steel
valve to allow the heated water into the pool.
Example:
Set Water temperature = 28°C
On Differential = 10°C
The valve will be opened when 38°C is detected in the array.
The valve will remain open, delivering heated water to the pool until the ‘Set
Water Temperature’ is achieved or the temperature within the solar array has
fallen to the ‘Off Differential’ value
Example:
Set Water Temperature = 28°C
Off Differential = 2°C
The valve will close when 30⁰C is detected in the array.