On Differential Temperature

This mode is user adjustable between 2

°C

 and 60

°C

, the factory default is 10

°C

‘On Differential’ is the temperature difference between your Thermecro solar 

array and swimming pool water. When the ‘On Differential’ value is reached, the 

electronic stainless steel valve opens to allow the heated water back to your 

swimming pool. The ‘On Differential’ value can be changed to optimise the heat-

ing process according to the prevailing climatic and other influencing conditions, 

however, under most circumstances when ‘On Differential’ is set to a value be-

tween 10 - 12ºC this will provide the best all round seasonal heating performance 

in most climates.

To set the ‘On Differential Temperature’ press the         /         buttons until this mode 

appears on the display and O.K. to select. Press the         /         buttons to set the 

required temperature and then press the O.K. button to save that value in the 

memory.

6

ENGL
IS

H

Off Differential Temperature

This mode is user adjustable between 1

°C

 and 49

°C

 the factory default is 2

°C

‘Off Differential’ is also the temperature difference between your Thermecro solar 

array and swimming pool water. When the ‘Off Differential’ value is reached, the 

electronic stainless steel valve closes, allowing the solar array to begin the

heating process again. 

 

Содержание SR-DC

Страница 1: ...Thermecro Solar Digital Controller Installation Operating Manual...

Страница 2: ...ENGLISH www elecro co uk...

Страница 3: ...ture reference Important safety information Consult a qualified electrician Always isolate the unit from mains electricity and turn off the water supply before carrying out maintenance Always disconne...

Страница 4: ...g Hole centres for mounting Wiring Connection Details This equipment must be installed in accordance with the country regional requirements and regulations This equipment must be installed by a qualif...

Страница 5: ...cable glands and connected to the terminal block tighten the cable glands after the connections have been made Wiring Diagram NOTE The pump output is a signal only to override the existing time clock...

Страница 6: ...w Language Setting The factory default setting for the language is English To change to another language press the buttons until the desired language appears press OK to select and save DIGITAL DISPLA...

Страница 7: ...est you set the required temperature on your traditional heater electric gas heat pump to 1 C or 2 C below the Set Water Temp selected This will ensure your system will operate as efficiently as possi...

Страница 8: ...s when On Differential is set to a value be tween 10 12 C this will provide the best all round seasonal heating performance in most climates To set the On Differential Temperature press the buttons un...

Страница 9: ...ar array press the buttons until Fill System mode appears on the display press O K this turns the filtration pump and the electronic valve On see diagram 1 and 2 When the array is fully purged of air...

Страница 10: ...n differential temperature the controller will open the stainless steel valve to allow the heated water into the pool Example Set Water temperature 28 C On Differential 10 C The valve will be opened w...

Страница 11: ...sed of correctly you will help prevent potential negative consequences for the environment and human health which could otherwise be caused by inappropriate waste handling of this product The recyclin...

Страница 12: ...11 Gunnels Wood Park Stevenage Hertfordshire SG1 2BH United Kingdom t 44 0 1438 749 474 f 44 0 1438 361 329 e sales elecro co uk www elecro co uk Copyright 2017 Z INS SR DC...

Отзывы: