Set Auto
0(0x00) = Disable AUTO report
func-
tion (Default)
(for saving battery life)
Auto report if room temperature is
different from last report.
1(0x01) = 1°F (0.5°C)
2(0x02) = 2°F (1°C)
3(0x03) = 3°F (1.5°C)
4(0x04) = 4°F (2°C)
5(0x05) = 5°F (2.5°C)
6(0x06) = 6°F (3°C)
7(0x07) = 7°F (3.5°C)
8(0x08) = 8°F (4°C)
1
Report
Condition
Trigger
30 (0x1E
By Room
Temperature
Change
Set Auto
Report
Condition
By
Time Interval
34 (0x22)
Auto report by the following time
interval.
1(0x01) = 1 Hr
2(0x02) = 2 Hrs
3(0x03) = 3 Hrs
4(0x04) = 4 Hrs
1
5(0x05) = 5 Hrs
6(0x06) = 6 Hrs
7(0x07) = 7 Hrs
8(0x08) = 8 Hrs (Default)
Note:
All the above Parameter Number and Value is in Hexadecimal
Numbering Format,
if the Gateway only support decimal numbering format, please change
it to decimal value accordingly.
Reset to Factory Default
Press and Hold “PROG” button for 3 seconds on AC Master, the
Green Indicator will light up. DO NOT Release the “PROG”
Button until Green Indicator flashes TWICE.
Z-Wave
TM
Notification
After the device adding to the network, it will wake-up once per day in
default. When it wake-up it will broadcast the “Wake Up Notification”
message to the network, and wake-up 10 seconds for receive the
setting commands.
To wake-up the device immediately, please hold down the program key,
and press the top-right key once.
Z-Wave
TM
Message Report
When the panic triggered, the device will report the trigger event and
also report the battery status.