02/2017 - Art. Nr. 4200 1015 6700D
22
Start up
Adjustment data
Checking the combustion head
1. ..
Distance from oil nozzle - air nozzle
Positioning of ignition electrodes
4
e
: 1.20/24/28/30
2
e
: 1.35/47
The setting template included with the
burner can be used for the following
functions.
Ignition electrode settings
IRD probe setting
Burner in operation.
• Turn potentiometer
A
back on the
probe until the 1st LED goes out.
• Turn the potentiometer up 2 scale
values. (flame signal must remain
>3µA)
The setting data above corresponds to
basic settings.
The factory-set
adjustment values are outlined in bold.
These adjustment values are normally
suitable for commissioning the burner.
Always check the adjustment values on
a case by case basis. System-specific
corrections may be necessary.
The following nozzle types are
recommended to achieve favourable
combustion values:
Danfoss 80°S
Danfoss 60°S
Delavan 80° B.
Bur ne r
Bur ne r output
k W
Air
nozzle
Ø
m m
Danfos s
GpH
nozzle
Nozzle
type
Pum p
pr e s s ur e
bar
Air volum e
s cale
Exhaus t gas
r e cir culation
ope ning s cale
Oil-air
nozzle
dis tance
m m
Air intak e
adjus te r
s cale
11
19
0,30
7,5
2
2
2,5
1
15
19
0,30
14
5
2
2,5
1
20
19
0,30
24
9
2
2,5
1
15
19
0,40
11
5
2
2,5
1
17
19
0,40
14
6
2
2,5
1
20
19
0,40
19
9
2
2,5
1
18
22
0,45
10
6
3
2,5
1
21
22
0,45
14
8
3
2,5
1
24
22
0,45
17
10
3
2,5
1
20
22
0,50
11
7
4
2,5
1
23
22
0,50
14
9
4
2,5
1
28
22
0,50
20
18
4
2,5
1
25
24
0,55
11
9
4
2,5
1
28
24
0,55
14
12
4
2,5
1
30
24
0,55
15
18
4
2,5
1
28
26
0,60
11
9
3
2,5
1
31
26
0,60
14
12
3
2,5
1
35
26
0,60
18
18
3
2,5
1
38
26
0,65
16
4
4
2,5
*
42
26
0,75
14
7
5
2,5
*
46
26
0,85
15
18
6
2,5
*
V B 1.20
60° S
60° S
80°S
V B 1.24
V B 1.28
V B 1.35
80°S
V B 1.47
80° S
V B 1.30
80°S