56
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory settings
0 NETWORK
0. 2 BUS Network
0. 2. 0
Network Presence
Indication of devices connected via BUS
Boiler
Remote Modem
OpenTherm Gateway
1
0. 4 User interface
0. 4. 0
Zone to be set by display
1 - 3
1
0. 4. 1
Backlight timing
1 min - 24 hours
10
min
0. 4. 3
Time Program service type
Select the time program service type
according to Ebus devices present in your
network
0 = Time programs
1 = Extended time
programs
0
0. 4. 4
Reset System Interfce
OK = Yes, BACK = No
4 Zone1 Parameters
4. 0 Setpoint
4. 0. 0
T Day
Room temperature set point for day period
10 - 30 (°C)
20
4. 0. 1
T Night
Room temperature set point for night
period
10 - 30 (°C)
15
4. 0. 2
T set Z1
Temperature setpoint zone 1
(
Limited by Para 4.2.5 and Para 4.2.6
)
40
°C - 82°C
20
°C - 45°C
75
20
4. 0. 3
Zone frost temperature
2 - 15 (°C)
5
4. 1 Summer/Winter Changeover
4. 1. 0
S/W function activation
0 = OFF, 1 = ON (only active when outside
temperature influence)
0 - 1
0
4. 1. 1
S/W temperature threshold
0 - 30 (°C)
15
4. 1. 2
S/W delay time
Time before S/W changeover becomes
active
0 - 300 (min)
30
4. 2 Zone1 Settings
4. 2. 0
Zone temperature range
0 = Low Temp (LT)
1 = High Temp (HT)
0 - 1
1
4. 2. 1
Thermoregulation
0 = Fix Flow T
1 = Basi Thermoreg
2 = Room T Only
3 = Outdoor T Only
4 = Room+Outdoor T
0 - 4
0