INSTALLATION

29/56

EN

 

drain any fuel still inside the burner and in the fuel delivery pipe and collect it in a basin

 

loosen the pipe clamp (7) and remove the air intake pipe (8), if present

 

8

7

Fig. 25 

 

loosen the nut (9) securing the burner to the boiler and, rotating the burner (10) slightly to the 

right, slide it off the boiler.

 

10

9

Fig. 26 

CAUTION

Dispose of any fuel that comes out of the burner in accordance with applicable legislation in the 

destination country. Separated waste management avoids potential damage to the environment 

and peoples’ health. It also allows many recyclable materials to be recovered, with significant 

economic and energy savings.

CAUTION

Содержание Firebird FB 4 R LN

Страница 1: ...FB 4 R LN LOW NOx LIGHT OIL BURNER Instructions to Assembly Commissioning and Maintenance EN Before installing and using the burner read this manual carefully and keep it close to the burner...

Страница 2: ...needed This manual contains important guidelines and suggestions which should be complied with in order to obtain a simple installation and the best possible use of the appliance RANGE This manual ref...

Страница 3: ...Two pipe system 13 2 6 1 Operating function 13 2 6 2 Controlled shutdown 14 2 6 3 Safety function 14 3 TECHNICAL DATA 15 3 1 Dimensions and weights 15 3 2 Technical data 16 3 3 Electrical diagram 17 4...

Страница 4: ...for safety 38 6 2 1 List of parts typically subject to wear 38 6 3 Removing the burner 39 6 4 Burner maintenance 42 6 4 1 Cleaning and replacing combustion head components 42 6 4 2 Diffuser position c...

Страница 5: ...to act as a heat source for heating and DHW generation systems in which water is the heating fluid Any other or wider application is outside of the specified intended use To avoid risks the burner sho...

Страница 6: ...t information that you must bear in mind 1 3 2 Other symbols DANGER FLAMMABLE MATERIAL Indicates a dangerous situation that could cause serious injury death or long term health risks caused by the pre...

Страница 7: ...or users and operators These risks derive from risk analyses carried out by Research and Development staff as required by European Standard EN 267 and applicable directives Machine directive LVD EMC D...

Страница 8: ...igh level of efficiency and thanks to a powerful transformer cold starts don t cause problems The operation of FB 4 R LN burners is reliable even in the event of persistent or intermittent wind igniti...

Страница 9: ...201 8 12 17 58 B E H D I C A G F J A Burner code B Week and year of manufacture C Burner model D Factory power setting E Burner power output F Electrical supply G Protection level H Electrical consump...

Страница 10: ...the burner 10 9 5 4 3 7 8 6 2 1 1 Power indication LED 2 Connection PLUG IN between control box and ignition transformer 3 Snorkel 4 Air setting 5 Air intake 6 Air valve indicator 7 Housing for intern...

Страница 11: ...ombustion head 12 Burner fixing bolt 13 Burner flange supplied 14 7 pin plug 15 Electric motor for pump and fan 16 Capacitor 17 Extended pressure port 18 Burner base 19 Oil pressure regulator 20 Fuel...

Страница 12: ...56 EN 2 4 2 Structure of the combustion head 1 5 6 4 3 2 7 6 1 Combustion head 2 Diffuser 3 Electrode group 4 Diffuser fixing screw 5 Electrode group fixing screw 6 Combustion head fixing screw 7 Noz...

Страница 13: ...ating logic Two pipe system M M1 118 103 101 120 T1 104 102 106 105 Y1 M1 Burner motor T1 Ignition transformer Y1 Solenoid valve 101 Fan 102 Oil pump 103 Air flap 104 Oil pressure regulator 105 Flexib...

Страница 14: ...duced after an unsuccessful restart attempt in the event of 5 flame failures during operation A safety shutdown is indicated by the malfunction lamp lighting up and it is then only possible to reset t...

Страница 15: ...s and weights 306 150 75 72 161 156 206 98 i 100 145 10 1 0 175 151 5 126 5 4 5 4 5 15 Max Fig 7 Model Weight kg net with packaging FB 4 R 20 LN 7 1 9 5 FB 4 R 26 LN 7 1 9 5 FB 4 R 35 LN 7 1 9 5 All m...

Страница 16: ...ump coil BFP T85 Electric motor EBR 90 W 2800 rpm 90 watt Capacitor Inco 4 F TEKNO 45T T top series Electrical supply 1 230 50 Ph V Hz Power consumption operation 10W 210 W 210 W 200 W Protection leve...

Страница 17: ...N Q MV YVg B R CONTROL BOX EBR M4 R 15 15 TV B4 S3 T2 T1 L1 N B4 S3 T2 T1 L1 N TV Ignition transformer B Photo resistor YVg Oil solenoid valve MV Fan motor HLB Security light HLF Operating light R Hea...

Страница 18: ...l Repeated and prolonged skin exposure to fuel oil can damage and irritate the skin take the following precautions as far as possible avoid contact with the skin use personal protective equipment such...

Страница 19: ...MATION Failure to observe these instructions will invalidate the warranty with respect to any damages caused by any of these causes 4 2 1 Flue gas system Before installation check the design suitabili...

Страница 20: ...ecks before mounting the burner Before mounting the burner onto the boiler check the distance between tips of electrodes 2 mm Fig 10 Check the position of the electrodes assuring that they are centere...

Страница 21: ...tallation position shown in Fig 12 Installation 2 3 and 4 are forbidden for safety reason OK 2 1 3 4 Fig 12 The burner is secured to the boiler using the connection flange supplied with the burner Fol...

Страница 22: ...ng torque of 3 5 Nm max insert the burner combustion head 6 with care inside the flange 1 5 2 6 Fig 14 rotate the burner first to the right and then to the left to insert the fastening screw 1 into th...

Страница 23: ...nd leave it switched off for approximately 3 hours to ensure degassing of the fuel and the deposit of suspended particles have any damage to the oil pipes repaired immediately by a specialised technic...

Страница 24: ...sure gauge port P1 Pressure adjustment R Return outlet S Suction inlet T Pressure regulator V Vacuum gauge port Fig 17 4 6 2 Oil pump 2 4 1 8 7 6 5 3 1 Fuel oil solenoid valve 2 Solenoid valve electri...

Страница 25: ...ws remove the cap 11 from the connection and screw in the additional return pipe 12 supplied with the burner 9 12 11 10 Fig 19 IMPORTANT INFORMATION There is an intake filter and an oil pressure regul...

Страница 26: ...0 mm 0 5 19 60 100 2 5 27 85 100 1 21 66 100 3 29 91 100 1 5 23 72 100 3 5 31 98 100 2 25 79 100 CAUTION X 20 m Y must be kept as lower as possible in order to avoid cavitation Anyway Y 4 m Burner hig...

Страница 27: ...3 Amps WARNING Use flexible cables in compliance with the EN 60 335 1 standard Assure a correct earth connection The wiring section must be minimum 1 mm2 in any case verify with the standard and local...

Страница 28: ...ns on the burner operate the main power switch for the system to cut off the power supply If it becomes necessary to remove the burner proceed as follows close the fuel taps upstream of the burner det...

Страница 29: ...rner to the boiler and rotating the burner 10 slightly to the right slide it off the boiler 10 9 Fig 26 CAUTION Dispose of any fuel that comes out of the burner in accordance with applicable legislati...

Страница 30: ...g The following must be checked before initial commissioning That the burner is assembled in accordance with the instructions given here That the burner is pre set in accordance with the values in the...

Страница 31: ...to the paragraph 5 3 Factory pre setting The installation of the burner on the boiler the commissioning and servicing must be carried out following the boiler technical manual including the check of t...

Страница 32: ...O2 O2 CO2 Fig 28 5 5 Adjusting burner output 2 4 1 8 7 6 5 3 1 Fuel oil solenoid valve 2 Solenoid valve electrical connection 3 Fuel delivery pipe 4 Vacuum port pressure gauge connection 5 Suction con...

Страница 33: ...adually if necessary Operating on air flap setting 5 6 Oil pressure setting 5 6 1 Oil pressure setting The oil pressure and therefore burner output is adjusted using oil pressure regulator 7 see Fig 2...

Страница 34: ...ing screws 3 using the key supplied 2 1 3 2 Fig 31 manually rotate the shaft 3 4 rotations both clockwise and anticlockwise Fig 32 refit the pump to the motor reconnect the oil pipe to the pump Check...

Страница 35: ...rs of the combustion system and record all the main data pertaining to the first ignition Explain to the proprietor and person responsible for the domestic heating system the burner is installed on th...

Страница 36: ...R 35 LN Serial number Output kW Nozzle size gph Spray angle cone type Fan pressure mbar Combustion chamber pressure mbar Air flap scale Oil throughput kg h Oil pressure oil pump bar CO2 Vol CO mg kWh...

Страница 37: ...superficial burns Operators should wear suitable clothing and personal protective equipment They should ensure that all components are at ambient temperature before carrying out any maintenance opera...

Страница 38: ...hecks 6 2 1 List of parts typically subject to wear Parts subject to wear should be regularly checked by the technician during maintenance operations and if necessary replaced Worn components Replacem...

Страница 39: ...tions on the burner operate the main power switch for the system to cut off the power supply To remove the burner from the boiler proceed as follows close the fuel taps upstream of the burner detach t...

Страница 40: ...o the boiler and rotating the burner 10 slightly to the right slide it off the boiler 10 9 Fig 36 CAUTION Dispose of any fuel that comes out of the burner in accordance with applicable legislation in...

Страница 41: ...nto the hole 12 on the burner base Use one of the three square grooves on the burner base to secure the burner which should be rotated to the best position for the maintenance operation to the carried...

Страница 42: ...unt the burner Start the burner check the exhaust gas data adjust the burner settings if necessary Fuel pipes should be checked annually and replaced after 2 years Check and clean the components on th...

Страница 43: ...ith the pin 3 1 2 3 Fig 39 6 4 2 Diffuser position check To check the position of the diffuser remove the combustion head as described in paragraph 6 4 1 Cleaning and replacing combustion head compone...

Страница 44: ...44 56 EN check the distance between the diffuser 1 and the nozzle 2 as shown in the figure 1 2 Fig 41 after having adjusted the position of the diffuser tighten the screw 8 refit the combustion head...

Страница 45: ...bustion head check the distance between the combustion head 1 and the nozzle 2 as shown in the figure 1 2 Fig 43 6 4 4 Electrode position check Check the distance between tips of electrodes 2 mm Fig 4...

Страница 46: ...built to withstand temperatures of up to 85 C In the event of malfunctions or faults replace the coil using the following procedure remove the connector 1 remove the nut 2 using the key supplied slide...

Страница 47: ...7 Cleaning the internal rotor Check there is no dust inside the fan wheel because this could reduce the combustion performances Carry out maintenance operations avoiding to damage the fan Verify the...

Страница 48: ...motor and blower wheel 3 The inside flange A of the blower wheel must be fitted at a lower position quote C than the equipment plate B tighten the set screw on the blower wheel A B 3 OK NO NO C Burner...

Страница 49: ...are not used on replacement These components must be replaced by parts with the same order number WARNING To reset the equipment control after viewing the visual diagnosis press the release button WA...

Страница 50: ...er Replace motor Check pump filter Remove false flame causes Unblock Replace pump Yes Yes Check pressure loss or complete system boiler fuel Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No...

Страница 51: ...flame sensor Replace control box Check flame sensor functionality Flame sensor work well Fig 51 Check flame sensor functionality Check procedure Take sensor on hands Obscure sensor to light Sensor see...

Страница 52: ...named FB 4 R LN is conform to the following standards EN 267 EN 55014 1 EN 60335 1 EN 61000 6 2 EN 50156 1 EN 55014 2 EN 60335 2 102 EN 61000 6 3 These products bear the CE mark in accordance with the...

Страница 53: ...ials including recycled cooking oil These types of oil must be considered and treated differently from common mineral and fossil fuels This is because they are more acidic hygroscopic and less stable...

Страница 54: ...a considerable amount of time Consult your biofuel distributor for the use of biocidal products to prevent microbial growth inside the tanks and for instructions on fuel filtering During the commissio...

Страница 55: ......

Страница 56: ...von PL7 5ET United Kingdom t 44 0 1752 691177 f 44 0 1752 691131 e sales firebird uk com web www firebird uk com ELCO Via Roma 64 31023 Resana TV Italy Tel 39 0423 719500 Fax 39 0423 719580 Company su...

Отзывы: