INSTALLATION
27/56
EN
4 .7
Electrical connection
DANGER
Danger of death caused by live components!
Contact with live parts can lead to serious injury, take the following precautions:
-
ensure that the power is switched off for all electrical parts
-
electrical wiring installation must be carried out by qualified personnel and in compliance with
the regulations currently in force in the country of destination. Refer to the wiring diagrams.
CAUTION
-
The electrical installation should include a minimum of a type A MCB.
-
Check to ensure that the power supply voltage is as specified in the electric diagram and in
data plate.
-
Burner fuse: 3 Amps.
WARNING
-
Use flexible cables in compliance with the EN 60 335-1 standard. Assure a correct earth
connection.
-
The wiring section must be minimum 1 mm
2
(in any case verify with the standard and local
rules).
-
This control flame is equipped with the post ventilation function. Other versions of the burner
are not to be fitted.
-
Check operation of boiler thermostatic control.
-
Check operation of Photocell by withdrawing from burner and then covering to simulate flame
out condition.
4 .7 .1
Electrical connection to the boiler
Burner
FB 4 R LN
leaves the factory configured for connection to a 7 pin electrical cable.
A 7 pins plug is also supplied and factory mounted.
Proceed as follows to connect the burner to the boiler:
–
connect the cable coming from the boiler to the 7 pins plug (1) (supplied).
1
from the boiler
Fig. 22
CAUTION
WARNING