Wherever an existing tank is to be used to store the oil, in addition to the above mentioned checks
on the materials, it is essential that the tank is first inspected to verify its condition and check for
the presence of water or other contaminants. If contaminants are found, a deep clean should be
carried out. If this is not carried out the hygroscopic nature of the fuel could dissolve and detach
complex components and cause faults in the equipment.
Based on the capacity of the storage tank and how the system is used, fuels can be stored
inside it for a considerable amount of time. Consult your biofuel distributor for the use of biocidal
products to prevent microbial growth inside the tanks and for instructions on fuel filtering.
During the commissioning of the burner, check that all combustion parameters are compliant with
the recommendations in the technical manual for the appliance.
Check the filters on the burner oil pipe and oil pump, and if necessary replace them:
–
at least every 4 months during burner use
–
before starting the burner following a long period of disuse
–
more often in the event of contamination.
CAUTION
Pay particular attention during the check and inspection to detecting fuel leaks from sealing
devices, gaskets and hoses.
CAUTION
IF Bio fuel is used consult your Bio fuel distributor.