06/2014 - Art. Nr. 4200 1057 7300
58
Initial start-up
Configuration data
Air adjustment
Air adjustment (A).
Intervene on screw A in the picture:
• turning it anti-clockwise increases
the flow rate;
• turning it clockwise decreases the
flow rate.
Note
: screw B not used.
The above adjustments are
basic
adjustments
. With these settings,
normally, the burner can be started up.
The adjustment must then be verified
using a combustion analyser.
It may be necessary to perform
corrections subject to the single plant.
Favourable combustion values can be
obtained using the
following nozzles:
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Adjusting the combustion head (B).
Intervene on the screw shown in the
picture:
• turn it using a hex spanner until it
reaches the desired value
(index from 0 to 5).
+
-
+
-
B
+
-
A
B
A
Burner
Burner power
kW
Fuel-oil flow
kg/h
Nozzle
60°B/W
Gph (Danfoss)
Pump pressure
bar
�
Firing head setting
mm
Air flap position
P2.190 L(SV)
74
6,2
1,75
8
0
1,5
130
11,0
2,50
12
1,0
2
169
14,3
3,75
11
3,0
4
P2.300 L(SV)
124
10,4
2,50
12
0
1,8
199
16,8
4,00
12
2
3
241
20,3
5,00
11
5
4
Bold : Delivery setting; 1kg fuel-oil at 10°C = 11.86kWh