19
SMS commands
The SMSB242/SMSB482 can be configured and controlled through a command set that can be sent by sms. The command
message is password protected (see chapter system password). The following is the command message format:
[PASSWORD]#[COMMAND]
for example: 0000#R1#1
(relay n.1 switch-on)
The password is always 4 character long plus #; the hash tag is a mandatory separator.
Commands can be linked and include spaces. ex. 0000#R1#1 R2#1 -> turns relays 1 and 2 on
The following table includes a list of SMS commands with their relevant description and example:
Command
Description
Example
[PW]#R[1-4]#0
deactivates relay outputs from 1 to 4
0000#R1#0
[PW]#R[1-4]#1
activates relay outputs from 1 to 4
0000#R1#1
[PW]#?
query on current status
0000#?
[PW]R[1-4]#T#[1-255]
generates a pulse from 1 to 255 seconds of the se-
lected relay
0000#R1#T#5
Special commands
Stop sequential mode
Send the QUIT[1-8] command when requested by the device through alarm SMS.
Ex. QUIT1
Activation without reply
To stop receiving the replying message from the device, add the following code:
-NR
(meaning: no reply)
Ex. pulse without reply: 0000#R1#T#5-NR (activates relay 1 for 5 seconds and does not send any confirmation)