MEM-BUS
EtherNet/IP™ ENCODER
Instruction Manual
ENIP_Manual_ENG 17/07/2018
11
2.6 IP Address S/W Setting
1.
Set the rotary switches to
888
and take a cycle power in order to load the default factory settings.
2.
Set the rotary switches to
000
and take a cycle power in order to enable S/W configuration.
3.
Run
RXLinx Classic Lite
for Rockwell Automation networks.
ELAP MEM-BUS encoder appears in the main window, with its default IP address (192.168.1.123).
Click the right mouse button and select
Module Configuration
command.
In the “Port Configuration” table, it is possible to configure the TCP/IP interface (see attributes 3 e 5 of
object F5, section 3.4).