![EKOS EKOSync 1588A Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/ekos/ekosync-1588a/ekosync-1588a_user-manual_2374273005.webp)
4
EKOSync 1588A User Manual rev 1.1
August 2021
EKOSync 1588A PTP TIME SERVER
I. FEATURES & SPECIFICATIONS
1
Description
EKOSync 1588A PTP Time Server provides sub-microsecond accuracy time information
for synchronizing energy distribution subsystem intelligent electronic devices, and proceeding
according to IEEE 1588 v2 time protocol. Product includes adjustable hold-over times for
discontinuities with GPS communication, and compensation for antenna reception distortions.
2
Features
DC IRIG-B (Unmodulated, DCLS - C37.118, not ready in this version)
TCP/IP remote M&C management option
Synchronized TOD (Time of Day) and PPS (Pulse per second) outputs
User defined 10MHz/5MHz frequency output
TCP/IP configuration option
NTP/ SNTP (IEC 61850)
IEEE 1588 PTP Server
18-75VDC or 90-240VAC (DC) Isolated power supply
Password protection and user authentication
3
Specifications
Electrical:
Input
Power Supply
Voltage:
18 to 75 V DC
90 to 240VAC (DC)
Power consumption: 10W max
Ethernet (RJ45 UTP)
10/100/1000 Mbps
Isolation
Power to GPS input
3 kV
Power to I/O
3 kV
Outputs
Relay output
250V 2A
4 TTL outputs
Time codes or pulses or user defined
Electrical specification:
TTL/CMOS compatible 0-5 V, 150 mA
sink/source