background image

CATALYST

It is recommended that the catalytic converter is inspected for signs of damage and dirt during routine serv-
icing procedures. The expected life of the catalyst is in excess of 11,000 hours (10 years of normal use).
After this time the catalytic converter should be replaced.

If there are any deposits of dirt or soot on the catalyst they should be cleaned with a soft brush and a vac-
uum cleaner. If removed for cleaning ensure the seals are in good condition before replacing the catalytic
converter. New seals will usually be required.

The performance of the catalyst may be checked using an analyser as follows. Any analyser used should
conform to BS7927 : 1998 + A1 : 1999 or BS EN 50379-3.

Important: The temperature of the gases emmited by the catalytic converter is in excess of 400 

o

C.

Measuring gas of this temperature may damage some types of gas analysers. If in doubt consult the
equipment manufacturer.

Position gas sample probe directly in front of the catalyst underneath the hood, in the centre of the upper
firebox. Ignite the fire as per the operating instructions, and run at high setting for 15 minutes. Record the
carbon dioxide (CO2) concentration and then the carbon monoxide (CO) concentration as displayed by the
analyser - also noting the units in which the values are expressed. 

Most analysers display carbon dioxide (CO2) concentrations in percentage (%) terms and carbon monoxide
concentration in parts per million (ppm) terms.

In order to calculate the combustion ratio for the appliance (CO/CO2) it is first necessary to express both
gas concentrations in terms of percentage. To convert from parts per million (ppm) to a percentage (%)
divide the ppm figure by 10,000. Examples : 35ppm = 0.0035%, 15ppm = 0.0015%, 5ppm = 0.0005%.

Now divide the concentration of carbon monoxide (CO) expressed in percent by the concentration of car-
bon dioxide (CO2) to obtain the appliance combustion ratio.

The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0.0015.

If replacing the catalytic converter, remove the
hood, front fret/facia and the grille (as shown in
figure 22). The catalytic converter retaining
clamp is secured with 4 nuts and slip proof
washers, located on the inside of the firebox, at
the top, remove these nuts and the clamp can be
removed. Withdraw the clamp, followed by the
catalytic converter and its seals from the firebox
and discard.

Refit a new catalytic converter and seal in
reverse order. 

TESTING FOR FIREBOX LEAKAGE

Appliances that are several years old or have been extensively dismantled should be checked for sound-
ness. It is important that all the products of combustion pass through the catalytic converter at the top of
the firebox before leaving the appliance. 

The firebox is heated by lighting for a few minutes to provide a flow through the firebox. The burner is
then shut off and a smoke pellet or match introduced at the base of the fire underneath the burner tray.
Large quantities of smoke will emerge from the top of the appliance, but none should emerge from the
joints or gasket faces, especially around the door. 

It is important to note that the appliance can never be expected to be 100% smoke tight and small quan-
tities of smoke may be seen in corners of joints and gasket faces etc without affecting safety when the
fire is in operation.

9.4

9.5

CO (%)
CO2 (%) = ratio

Figure 22

14

©

2009 Focal Point Fires plc.

Содержание eko 5510

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision B 08 11 Country s of destination GB IE eko 5510 eko 5520 eko 5530 high efficiency flueless gas fire...

Страница 2: ...Eko 5510 2009 Focal Point Fires plc Eko 5520 Eko 5530...

Страница 3: ...ource of heat then conden sation may occur on colder surfaces within the room On first light up of a new appliance initial curing of high temperature paint and burning off of lubricants may occur for...

Страница 4: ...may include adjacent spaces but these spaces must not be separated by a door To calculate a room size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This applia...

Страница 5: ...led is carpeted or has a fabric floor covering then a small solid hearth will be required meeting the dimensions specified in table 1 and illustrated in figure 2 In all installations the wall or back...

Страница 6: ...m 4 but curtains drapes and other fabrics are not permitted within a distance of 500mm 20 of the appliance sides No such materials are permitted direct ly above the appliance regardless of distance Th...

Страница 7: ...cycling centre COMPONENT CHECKLIST APPLIANCE INSTALLATION Note Ensure that the gas supply is isolated before commencing installation of the appliance The fireplace opening and environment must be in c...

Страница 8: ...d Pipes must be secured using suit able clips and protected against corrosion Ideally factory finished protected pipework and fittings should be used Joints should be kept to a minimum and compression...

Страница 9: ...and squarely over the fire place opening and if possible centrally under a block joint Clear out the block work in the area and insert the lintel by saw or stitch drill and chisel Do not dry bed the...

Страница 10: ...possible into and out of the area behind the fire without excessive heat loss from the room when the fire is off Installation as per method 2 recessing into a wall When setting the appliance into the...

Страница 11: ...ly insert the firebox into the opening and guide the gas pipe through the sealing grommet into its final routing position and fit the restrictor inlet elbow supplied to the gas pipe Secure the firebox...

Страница 12: ...Fit the fuel bed as described in section 7 3 All models The gap between the spark electrode and the pilot should be 3 5mm to produce a good spark There should be no need to adjust this If under any c...

Страница 13: ...NCE The control knob is supplied in the loose parts pack Fit the control knob onto the valve spindle as shown in figure 19 The pilot is visible behind the left hand side of the burner Push in and turn...

Страница 14: ...for regular servicing Frequency of service depends on usage but MUST be carried out at least once annually Advise that cleaning of the fire maybe achieved when the fire is cold using a damp cloth and...

Страница 15: ...em and should not be taken apart Aeration holes must be absolutely clear internally for proper operation NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT Modifications are dangerous...

Страница 16: ...percentage To convert from parts per million ppm to a percentage divide the ppm figure by 10 000 Examples 35ppm 0 0035 15ppm 0 0015 5ppm 0 0005 Now divide the concentration of carbon monoxide CO expre...

Страница 17: ...as a hole holes through which there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or...

Страница 18: ...i ance become naturally hot during use It is recommended that a suitable fireguard is used especially where young children pets the elderly or infirm are concerned The manufacturer of this appliance c...

Страница 19: ...terials Combustible materials are defined as wood fabrics or other materials likely to combust if exposed to flame Generally any material which is likely to discolour melt or misshape when exposed to...

Страница 20: ...control knob is marked as shown in figure 1 The pilot is visible behind the left hand side of the burn er Push in and turn the control knob to the SPARK position and hold there for a few seconds Cont...

Страница 21: ...glass cleaner Test on a small area first PAINTED AREAS These can be cleaned using a dry cloth FINISHED METAL AREAS These can either be cleaned using a proprietory metal cleaner or baby oil Test on a...

Отзывы: