En
gli
sh
- 3 -
User manual EK-TM1-TP
TECHNICAL FEATURES
• Power supply: 115 ÷ 230 Vac (-15% ÷ +10%) 50/60 Hz
• Power consumption: 7 VA (2.6W)
• Lithium backup battery: 3V, CR14250 type (replaceable)
• 9 available channels
• Terminals for:
- device power supply (terminals 1-2)
- auxiliary power supply output of 12V dc ±10%, 80mA, 1W
(compatible with EK-GPS-1 power supply) (terminals 3-4)
- communication bus for the connection of the EK-GPS-1
additional module (terminals 5-6)
- monostable change-over relay with maximum switchable
load of 16A / 250V (terminals 7-8-9)
• Terminal block for cables with maximum cables section
of 2.5 mm
2
• Display LCD with backlight (active with AC power supply)
• Storable programs: 450 (900 events) (divisible on 9 channels)
• Actions type: 1B
• Operating temperature: 0 ÷ 50 °C
• Operating humidity: 20 ÷ 90% non condensing
• Storage temperature: -10 ÷ + 70 °C
• Container: 3 DIN modules
• Protection degree: IP20
• Insulation: reinforced between accessible parts (front) and all
the other terminals
EN
Содержание EK-TM1-TP
Страница 2: ......
Страница 36: ...Italiano 34 Manuale d uso ekinex EK TM1 TP Men Programma nuovo astro notte Scegliere notti Programmi notte...
Страница 53: ...Italiano 51 Manuale d uso ekinex EK TM1 TP...
Страница 55: ...Italiano 53 Manuale d uso ekinex EK TM1 TP 2...
Страница 92: ...English 34 User manual EK TM1 TP Program menu new astro night Choose nights Nights programs...
Страница 103: ...English 45 User manual EK TM1 TP Choose the channel Choose the period Choose the type Check programs...
Страница 105: ...English 47 User manual EK TM1 TP Choose the channel Choose the period Choose the type Modify Delete programs...
Страница 109: ...English 51 User manual EK TM1 TP...
Страница 111: ...English 53 User manual EK TM1 TP 2...
Страница 115: ......