2

For the installation of the device on the rail proceed as 

follows:
•  with the aid of a tool bring the locking device in the fully 

lowered position (1);

• 

place  the  upper  edge  of  the  rear  inner  profile  on  the 

upper edge of the rail (2);

•  rotate the device towards the rail (3);

•  push the locking device upward until it stops (4).
Before removing the device, be sure the inputs have been 

disconnected and the bus terminal has been extracted 

from its slot. Use a screwdriver to slide down the locking 

device and remove the device from the rail.

Mounting

The device has degree of protection IP20, and is there-

fore suitable for use in dry interior rooms. The housing is 

made for rail mounting according to EN 60715 in boards 

or cabinets for electrical distribution. The installation is in 

horizontal position, the correct position is when the KNX 

bus terminal and the 110-230 Vac terminals are located at 

the bottom and the terminals for the outputs are located 

at the top.  

Switching, display and connection elements

The device is equipped with a programming pushbutton 

and a programming LED, membrane pushbuttons, LED 

for status indication and terminals for connecting the KNX 

bus line, the 110-230Vac power supply and the outputs.
Switching elements
•  Pushbutton (3) for switching between the normal and 

programming operating mode

•  Pushbutton (7) for switching between the operating mo-

des: forced (pushbuttons on the front panel: active) or 

automatic (pushbuttons on the front panel: not active)

•  Pushbuttons (2) for forced operation of the output chan-

nels

•  Rated voltage (U

n

): 100-230 Vac 50 / 60Hz

•  Rated current (I

n

): max 16 (10) A (both @ 100Vac and 

@ 230Vac)

•  Max switched power: max 4000 VA @ 250Vac

•  Inrush current: 88 A 20 ms

Environmental conditions
•  Operating temperature: - 5 ... + 45°C

•  Storage temperature: - 25 ... + 55°C

•  Transport temperature: - 25 ... + 70°C

•  Relative humidity: 95% not condensing

EKINSTGUIDAEKAB1TP

1

2

4

3

Connection of the KNX bus line

The connection of the KNX bus line is made with the ter-

minal block (black/red) included in delivery and inserted 

into the slot of the housing.
Characteristics of the KNX terminal block
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm

•  recommended wire stripping approx. 5 mm

• 

color  codification:  red  =  +  (positive)  bus  conductor, 

black = - (negative) bus conductor

Thanks to the pushbuttons located on the front of the de-

vice, the connected loads can be manually controlled in 

the absence of voltage on the KNX bus or when the pro-

gramming has not yet been carried out, and in this way it 

is possible to check the functioning of the loads. In these 

conditions, however, it is not possible to have the status 

feedback through the LEDs.

Connection of the 110-230 Vac power supply

The connection of the 110-230Vac power supply (fig. a) is 

made with the screw terminals located on the lower front 

of the device.

1B

2B

3B

8B

1A

2A

3A

8A

EK-FF1-TP

16xD.O. 16(10)A/230Vac 

~

 50/60 Hz

8xBlind 16(10)A/230Vac 

~

 50/60 Hz

4B

5B

4A

5A

6B

7B

6A

7A

3

4

1A

A

B

19

20

1B

21

22

2B

23

24

3B

25

26

4B

27

28

5B

29

30

6B

31

32

7B

33

34

8B

5

6

2A

A

B

7

8

3A

A

B

9

10

4A

A

B

11

12

5A

A

B

13

14

6A

A

B

15

16

7A

A

B

17

18

8A

A

B

1

2

L

N

bus KNX

230V~ 50/60Hz

1) Terminal blocks for output channels

2) Pushbuttons for forced operation of the inputs

3) Programming pushbutton

4) Programming LED 

5) Terminal block for KNX bus line

6) Terminal blocks for 230 Vac 50/60 Hz power supply

7) Pushbutton for switching between manual and automatic operation

8) LED for indication forced / automatic operation mode 

9) LED for status indication of the outputs

DCEKFF1TP

1

2

4

5

8
7

6

3

9

Warning!

 In order to supply the KNX bus lines use 

only KNX bus power supplies (e.g. ekinex EK-AB1-

TP or EK-AG1-TP). The use of other power supplies 

can compromise the communication and damage 

the devices connected to the bus.

!

Note.

 It is recommended that the installation of the 

device always ensure the full accessibility of the 

front side to allow the operation of the pushbuttons.

i

Note.

 In case of failure of the bus voltage, the 

switching of the loads is possible only if they are still 

powered with the mains voltage 110-230 Vac. The 

relay status in case of failure and reset of the bus 

can be set during the device configuration.

i

Display elements
•  Red LED (4) for displaying the active operating mode of 

the device (on = programming, off = normal operation)

•  Green LEDs (9) for displaying the switching status of 

the output channels (on = closed contact, off = opened 

contact)

•  Red LED (8) for displaying the operating mode (on = 

forced operation, off = automatic operation)

Содержание EK-FF1-TP

Страница 1: ...h LEDs Configuration as normally opened or normally closed switch Logic gates and forced operation mode Status feedback only at bus operating Locking function for each channel Time programming delay for switching on and off stai rcase lighting function with prewarning signal Integration in scenes Counter of operating hours configurable by bus Control of blinds The device can be used for switching ...

Страница 2: ...le wire conductors and diameter between 0 6 and 0 8 mm recommended wire stripping approx 5 mm color codification red positive bus conductor black negative bus conductor Thanks to the pushbuttons located on the front of the de vice the connected loads can be manually controlled in the absence of voltage on the KNX bus or when the pro gramming has not yet been carried out and in this way it is possi...

Страница 3: ...s must be cle arly identified Controlling loads with mobile installa tion e g household appliances connected to mains sockets must be planned and realized with a care ful evaluation of the risks that may arise in the case of control without direct visual contact with the load remote control Connecting loads different than those planned remote controlling without direct ve rification of the current...

Страница 4: ...tallation electrical connection configuration and commissioning of the device can only be carried out by qualified personnel in compliance with the applicable technical standards and laws of the respective countri es Warning Incorrect disposal of this product may cause serious damage to the environment and hu man health Please be informed about the correct disposal procedures for waste collecting ...

Отзывы: