background image

3

Configuration
For the configuration of the device parameters the corre

-

sponding application program or the whole ekinex

®

 pro-

duct database must be loaded in the ETS program. For 

detailed information on configuration options, refer to the 

application manual of the device available on the website 

www.ekinex.com

1B

2B

3B

4B

1A

2A

3A

4A

EK-FE1-TP

8xD.O. 16(10)A/230Vac 

~

 50/60 Hz

4xBlind 16(10)A/230Vac 

~

 50/60 Hz

3

4

1A

A

B

5

6

2A

A

B

7

8

3A

A

B

9

10

4A

A

B

11

12

1B

13

14

2B

15

16

3B

17

18

4B

1

2

L

N

230V~ 50/60Hz

bus KNX

+

L

-

N

KNX

bus

230 Vac

50/60 Hz

a

Connection of the KNX bus network and 230 Vac power supply

Connection of the loads

The  connection  of  the  controlled  loads  (fig. b,  fig. c)  is 

made with the screw terminals located at the top. In case 

the device is used as 4-fold blind actuator, the terminals 

must be connected coupling the channels as follows: 1A-

1B, 2A-2B, 3A-3B, 4A-4B.
Characteristics of the terminals
•  screw clamping of conductors

•  maximum cross section of conductor 2.5 mm² (single-

wire) or 1.5 mm² (multi-wire)

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

Use as a blind actuator
The output contacts for the up / down directions are in-

terlocked so that no voltage is applied simultaneously on 

both contacts.

Configuration and commissioning

Configuration  and  commissioning  of  the  device  require 

the use of the ETS

®

 (Engineering Tool Software) program 

V4 or later releases. These activities must be carried out 

according to the design of the building automation system 

done by a qualified planner.

Product 

code

Application

program

(## = release)

Communica-

tion objects

(max nr.)

Group 

adresses

(max nr.)

EK-FE1-TP

APEKFE1TP##.knxprod

222

254

c

Connection of the loads (device used as 4-fold blind actuator)

4

3

1A

12

11

1B

M

L

N

6

5

2A

14

13

2B

M

8

7

3A

16

15

3B

M

10

9

4A

18

17

4B

M

Warning!

 The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off. 

!

Note.

 The configuration and commissioning of KNX 

devices require specialized skills. To acquire these 

skills, you should attend the workshops at KNX cer-

tified training centers.

i

b

Connection of the loads (device used as 8-fold binary output)

L

N

1A

2A

3

4

3A

5

6

4A

7

8

L

N

1B

11

12

2B

13

14

3B

15

16

4B

17

18

9

10

Warning!

 Sockets controlled via bus must be cle-

arly identified. Controlling loads with mobile installa

-

tion (e.g. household appliances connected to mains 

sockets) must be planned and realized with a care-

ful evaluation of the risks that may arise in the case 

of control without direct visual contact with the load 

(remote  control).  Connecting  loads  different  than 

those planned, remote controlling without direct ve-

rification of the current conditions of the connected 

load or automatic controlling based on scenes or 

time-scheduling can cause serious damage to pe-

ople and objects. 

!

Commissioning
For commissioning the device the following activities are 

required: 
•  make the electrical connections as described above; 

•  turn on the bus power supply; 

•  switch the device operation to the programming mode 

by pressing the programming pushbutton located on 

the front side of the housing. In this mode of operation, 

the programming LED is turned on; 

•  download into the device the physical address and the 

configuration with the ETS

®

 program. 

At the end of the download the operation of the device 

automatically returns to normal mode; in this mode the 

programming LED is turned off. Now the bus device is 

programmed and ready for use.