background image

1

KNX bus power supply 1280 mA with 30 

Vdc auxiliary output

Product code: EK-AM1-TP

•  Cooling by free air convection

Main characteristics

•  Housing in plastic material

•  Mounting on 35 mm rail (according to EN 60715)

•  Protection degree IP20 (installed device)

•  Isolation class I

•  Safety class II

•  Overvoltage cathegory III (according to EN 61558, EN 

50178, altitude up to 2000 m. s.l.m.)

•  4 modular units (1 UM = 18 mm)

•  Dimensions 72 x 90 x 70 mm (WxHxD)

•  Weight: 296 g

Environmental conditions
•  Operating temperature: - 30 ~ + 70°C

•  Storage temperature: - 40 ~ + 85°C

•  Working humidity: 20 ~ 95% RH not condensing

•  Storage humidity: 10 ~ 95% RH not condensing

Technical data

Power supply
•  Mains voltage range 180 ~ 264 Vac, 176 ~ 280 Vdc 

•  Frequency range 47 ~ 63 Hz

•  Power consumption 38.4 W

•  Input AC current (typical) 0.5 A @ 230 Vac

•  Inrush current (typical): cold start 60 A (t

width

=1200 µs 

measured at 50% l

peak

) @ 230 Vac

•  Leakage current: < 1 mA @ 240 Vac

Outputs
•  Bus line voltage: 30 Vdc SELV

•  Auxiliary voltage: 30 Vdc SELV

•  Rated current (total outputs): 1280 mA

•  Short circuit current: 2.8 A

•  Setup, rise time: 1000 ms, 50 ms @ 230 Vac at full load

•  Ripple & noise (max): 100 mVp-p (*)

•  AC mains failure back-up time (typical): 200 ms @ 230 

Vac at full load

•  Bus line connection: KNX terminal block (black/red) in-

cluded in delivery

•  Auxiliary output connection: dedicated screw terminal 

block

KNX device with function of power supply for a bus line 

with auxiliary output. It has to be used in KNX installations 

for control of homes and buildings.

Description

The ekinex

®

 power supply EK-AM1-TP is a KNX device 

for rail mounting which produces and monitors the 30 Vdc 

voltage required to operate the bus system. It has a 30 

Vdc additional output, which can be used as a SELV (sa-

fety extra low voltage) auxiliary power for bus devices. 

The device has an integrated choke which provides the 

decoupling between the power supply and the information 

on the bus line. On a KNX bus line can be connected up 

to 256 KNX bus devices. The output is protected from 

overload, short circuit and overvoltage. The total current 

absorbed by the two outputs (KNX bus and auxiliary) can-

not exceed 1280 mA. The device can support short inter-

ruptions of the mains voltage (max 200 ms at full load).

Functions

•  30 Vdc SELV power supply for a KNX bus line with max 

256 connected devices (depending on the current con-

sumption of each device)

•  Auxiliary power supply 30 Vdc

•  Reset of the connected bus line with a dedicated pu-

shbutton

•  LED indicators for normal operation, bus reset and bus 

overload

•  Protections: overload, short circuit, overvoltage

Datasheet STEKAM1TP_EN

Protections
•  Overload: 205 ~ 235% rated output power. Protection 

type: constant current limiting, recovers automatically 

after fault condition is removed

•  Overvoltage: 33 ~ 35 V. Protection type : Hiccup mode, 

recovers automatically after fault condition is removed

Safety and EMC
•  Safety standards: EN 61558-1, EN 61558-2-16; EN 

50491-3

•  Withstand voltage I/P-O/P: 4, 2KVAC I/P-FG: 2KVAC

• 

Isolation resistance: I/P-O/P, I/P-FG: 100 MΩ @ 500 Vdc 

@ 25 °C @ 70% RH

•  EMC emission: compliance to BS EN 50491-5-2, -5-3; 

BS EN 61000-3-2, -3-3

•  EMC immunity: compliance to BS EN 50491-5-2, -5-3; 

BS EN 61000-4-2, 3, 4, 5, 6, 8, 11.

TP

S

REAEKAM1TP

(*) Note: Ripple & noise are measured al 20 MHz of bandwidth 

by using a 12’’ twisted pair-wire terminated with a 0,1 μF and 47 

μF parallel capacitor. The measure is done before the decoupling 

choke.

Содержание EK-AM1-TP

Страница 1: ...the 30 Vdc voltage required to operate the bus system It has a 30 Vdc additional output which can be used as a SELV sa fety extra low voltage auxiliary power for bus devices The device has an integrat...

Страница 2: ...m number of bus devices connected is 256 the maximum length of a line segment is 350 m me asured along the line between the power supply and the furthest bus device the maximum distance between two bu...

Страница 3: ...ted and the bus terminal has been extracted from its slot Use a screwdriver to slide down the locking device and remove the device from the rail Electrical connections Input main supply The connection...

Страница 4: ...e appli cable technical standards and laws of the respective countries The use of the device in security applications is not allowed The device may however be used for auxiliary signaling functions Op...

Страница 5: ...ssed to the EKINEX technical support in case of malfunctio ning of the device KNX and ETS are registered trademarks of KNX Association cvba Brussels EKINEX S p A The company reserves the right to make...

Страница 6: ...bus devices can not exceed 700 m the maximum length of a bus line is 1000 m keeping into account all segments It is possible to connect two EK AM1 TP in parallel with the following conditions two cho...

Страница 7: ...7 Annex 3 Block diagram Annex 4 Characteristics Derating curve Static characteristics...