background image

GuaRdboX

 - 

Gd

 

series   

 

 

IOM 

(

Installation, Operation & Maintenance Manual)    0100-ENG 

rev.5 

                                      

    

        

 

 

Eisenbau s.r.l. a socio unico 

Via T.A:Edison, 16 20090 Cusago (MI) Italy                

Phone : +390293562116 Fax: +390293567735 

Guardbox production unit : Via XXIV Maggio, 13   

25017 – Sedena di Lonato (BS)   

Phone : +390309131240 Fax: +390309130946

        

 

 

www.eisenbau.it 

www.guardbox-ex.com 

 

 

 

1.

 

Introduction: 

This instruction manual contains important information regarding the safety instructions, installation, operation, maintenance and storage of 
the 

“Guardbox” limit switch boxes. 

The limit switch boxes may only be mounted, wired and installed by qualified and trained personnel, according to International standards 
requirements  for  hazardous  areas.  If  you  require  any  additional  information  or  assistance,  please  contact  the  manufacturer  or  its 
representative. All contacts are listed in the footnote together with the QR code for an easy access to the complete product documentation. 
Please read these instructions carefully before proceeding with the limit switch box installation and save them for future reference. 

2.

 

Product description: 

 

Guardbox  Limit  switch  boxes  are  electromechanical  devices  ideal  for  monitoring  the  remote  operation  of  industrial  valves  in  plants, 
designed and manufactured for demanding application in extreme environments and where there are requested high standards for safety 
and reliability products. The Guardbox devices are used to control the position of the valve and provide high accuracy electrical feedback 
signal of valve status to plant control systems. Guardbox devices are equipped in standard configuration with a 3D high visibility position 
indicator that  represent  a  true  indication  of  valve  position. The  indicator  is visible  on  all  4  sides  and  is fully  adjustable  on  360°  without 
disassembly. Guardbox limit switch boxes are built to be installed on valves or actuators which drive the process valves from  closed to 
open position (Normal acting) or from  open to closed position (Reverse acting) . 

Normal acting 

is considered full CW when the process 

valve is closed and CCW when the process valve is open. 

Reverse acting 

is full CW when the process valve is open and CCW when the 

process valve is closed.  

 

3.

 

  

Safety instructions: 

 

Guardbox  Limit  switch  boxes  are  electromechanical  devices  ideal  for  monitoring  the  remote  operation  of  industrial  valves  in  plants, 
designed and manufactured for demanding application in extreme environments and where there are requested high standards for safety 
and reliability products. The Guardbox devices are used to control the position of the valve and provide high accuracy electrical feedback 
signal of valve status to plant control systems. GD Guardbox explosion proof Exd series limit switch box are specially projected and built to 
withstand the most extreme weather conditions and be installed into

 

hazardous areas with flammable gases, vapours and mist, according 

with  the  relevant  Union  harmonization  legislation  of  ATEX  Directive  2014/34/EU,  and  to  IECEx  Scheme  and  applicable  standards. 
Reference  standards  are  the  IEC60079-0:2011  (Ed6.0),  IEC60079-1:2014  and  IEC60079-31:2013  (Ed2.0),  and  the  applied  marking  of 
Group, category and applied Ex protection

 

is:

  

 

    Ex 

– Equipment Marking           

                    

II2G  Ex db IIC T6

…T4 Gb 

                                                                             II2D  Ex tb IIIC T85°C

…T135°C Db 

 
 

     

Ex 

– Marks     

    

II      2      G              Ex    db       IIC             T6       T5      T4            Gb

     

      

 

 
 
 
 
 
 
 
 

                            

    

II      2      D               Ex  tb   IIIC      T85°C    T100°C    T135°C       Db

     

      

 

 

On  the  outside  of  the  Exd  box  cover  there  are  two  metal  nameplates  on  which  are  etched  and  marked  the  Ex-marking  and  all  the 
information and references about the manufacturer, electrical and ambient range of use of the specific product, together with a Data Matrix 
code for a quick link and easy access to the product documentation including wiring diagram, drawings, datasheet and certificates: 

 
 
 
 
 
 
 
 
 

group

 

category

 

Dust

- flammable

gas

 

Protection

 

concept

 

Dust group

 

Gas group

 

Tempera

ture

 

class

 

Max surface

 

temperature

 

Dust

-flammable 

- gas

 

Ex 

- Symbol

 

 

Содержание GuaRdboX GD Series

Страница 1: ...alves or actuators which drive the process valves from closed to open position Normal acting or from open to closed position Reverse acting Normal acting is considered full CW when the process valve i...

Страница 2: ...acteristics of the electrical connection are compatible with electrical operation parameters of operation of the box 3 5 Do not exceed the limit switch box performance limitation Exceeding the limitat...

Страница 3: ...r repair of the flameproof enclosure is permitted For additional assistance please contact the manufacturer 3 19 CAUTION The metallic alloy used for the housing material may be at the accessible surfa...

Страница 4: ...2 mm 6 4 The motion transmission from the actuator or valve to the box GD is attained by a mechanical coupling Before installation on a valve or an actuator make sure that the orientation of the posit...

Страница 5: ...3 Metric thread conform to UNI 5870 1971 NPT thread conform to ANSI ASME B1 20 1 1983 7 5 Unscrew the six box cover captive screws 8 then remove the box cover 7 7 6 Use cables suitable for temperatur...

Страница 6: ...s are factory presetted in order to operate in a box installed parallel See section 6 Mounting to CCW rotating actuators Normal acting The lower cam 1 is regulated to operate the switch in the full CW...

Страница 7: ...Pi PN inductive proximity inductive proximity namur Board assembly Turn the actuator pinion full CW and regulate the cam till the switch 1 is activated Turn the actuator pinion full CCW and regulate t...

Страница 8: ...tion of mounting screws bolts O rings and terminal wiring for signs of loosening or corrosion as part of the routine plant maintenance 10 3 Guardbox boxes have been projected to withstand the most sev...

Отзывы: