background image

1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

 

 

 

FIG. 2.3 

INSTALL THE DRIP PAN 

1.

 

Two hose fittings were provided with the drip pan, a right angle and a straight one.  Choose 
one and install it on the drip pan.  Be sure if you use the right angle fitting it is facing the 
desired direction prior to installing the drip pan. 

2.

 

There is one mounting hole in the drip pan, match this hole with the long mounting screw 

protruding into the enclosure at the bottom of the AC unit.  Push the drip pan onto this 
screw. 

2.800

3.000

3.000

2.800

2.800

2.800

0.175

0.175

11.250

5.250

Содержание AAC-140B-4XT

Страница 1: ...TIONS INC 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 400 Btu MODEL S AAC 140B 4XT AAC 140B 4XT HC AAC 140B 4XT XXXXX Cooling Solutions for Mission Critical Electronics ...

Страница 2: ...PARING THE ENCLOSURE 6 2 4 INSTALLING THE AIR CONDITIONER 6 INSTALL THE DRIP PAN 7 APPLY POWER 8 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 10 3 2 MAINTENANCE 10 EIC SOLUTIONS INC 1825 STOUT DRIVE WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 07 Rev D 3 232012 ...

Страница 3: ...from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside...

Страница 4: ...or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 400 Btu units are always mounted with the exposed heatsink fins at the bottom and the fans at the top Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP 140V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidity levels qual...

Страница 5: ...F AC INSIDE OF ENCLOSURE DRAIN TUBE ENCLOSURE DP 140V DRIP PAN HOT SIDE FAN COLD SIDE FAN HOT SIDE HEAT SINK FINS COLD SIDE HEAT SINK FINS HORIZONTAL INSTALLATION OF AAC 140B 4XT 400 BTU UNIT WITH INTERNALLY MOUNTED DP 140H DRIP PAN AND DRAIN TUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FAN HOT SIDE FAN COLD SIDE HEAT SINK FINS HOT SID...

Страница 6: ...rners of the section to be cut out 5 Remove the stencil and using a pencil or other method connect the marks you made at the corners of the cut out forming a rectangle 6 Using the jigsaw cut the opening in the enclosure 7 Using the 29 drill bit drill a hole at each of the mounting hole marks you made earlier 8 Using the 8 32 tap tap each of the holes you have drilled 2 4 INSTALLING THE AIR CONDITI...

Страница 7: ...nstall it on the drip pan Be sure if you use the right angle fitting it is facing the desired direction prior to installing the drip pan 2 There is one mounting hole in the drip pan match this hole with the long mounting screw protruding into the enclosure at the bottom of the AC unit Push the drip pan onto this screw 2 800 3 000 3 000 2 800 2 800 2 800 0 175 0 175 11 250 5 250 ...

Страница 8: ...ALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT APPLY POWER Once the air conditioner is mounted check the serial label and confirm the voltage required and then apply appropriate power as outlined below 120 VAC units plug into standard 120 volt grounded outlet Amperage for a 120 VAC unit is 2 0 amps ...

Страница 9: ...hased a Digital Temperature Controller with your AC unit a separate wiring diagram has been provided which will show the correct method of applying power to your particular air conditioner Upon applying power to the air conditioner the fan on the cold side inside the enclosure will come on The hot side fan outside the enclosure may also run depending on where the thermostat is set The cold side fa...

Страница 10: ...nit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed using compressed air to blow out the heat sinks Do not direct any high press...

Отзывы: