background image

If the mains wires are being brought along the surface:
(a) position the mounting plate so the cable trunking is 

as shown in 

Figure 4

.

(b) the mounting plate has a removable section, take 

it out to interface directly with 25mm conduit as shown 

in 

Figure 5

. If interfacing to 16mm conduit carefully cut 

around the marked section, leaving the top intact and 

replace the section. (If you are not using surface wiring, 

the removable section must be left in place for electrical 

safety reasons).

There are two other positions which are also suitable for 

the surface wiring to enter (and exit) the Alarm, one next 

to the removable section and another directly opposite.

5.

 Carefully align the mounting plate and screw into 

place. Connect the wires to the terminal block. With 

recessed wiring, ensure the rear gasket seals around the 

edge of the hole in the ceiling or wall. This is to prevent 

air draughts affecting the smoke/heat entering the 

Alarm. If the hole is too large or the Alarm does not seal 

it, it should be sealed with silicone rubber or equivalent.

6.

 Carefully line up the unit on the base and slide on.

7.

 Press and hold the test/hush button for 10 seconds. The 

horn will sound. On release of the test button the local alarm 

will stop sounding immediately and the interconnected 

Alarms will stop sounding a few seconds later.

8.

 Connect the mains power to the alarm circuit. Check 

the green light is on. 

9.

 Attach the 

‘Smoke Alarm’

 identification label provided 

to the distribution board to identify the alarm circuit.

10.

 Attach the 

‘Mains Smoke / Heat Alarms’

 label 

provided on or near the distribution board and write in 

date installed and the number of Alarms on the circuit.

Ensure the Alarm operates correctly - see “

TESTING  & 

MAINTENANCE

” section on page 2.

15

REMOVEABLE

TRUNKING DOOR FOR

Figure 4

Figure 5

Содержание BROOKS EIB160e Series

Страница 1: ...interconnected Please contact your local distributor for more information Interconnection can be achieved by hardwire or through a modular RF module the EIB100MRF which can be inserted into the base o...

Страница 2: ...nds The cause of the alarm should be investigated After 24 hours the memory will be cleared 3 Press the test button for up to 10 seconds to ensure the sensor chamber electronics and sounder are workin...

Страница 3: ...g left without mains power for long periods the Smoke Heat Alarms should be removed from their mounting plates to prevent the batteries becoming fully depleted This is sometimes done with holiday home...

Страница 4: ...type When sure that it is just a nuisance false alarm simply press the test silence button briefly on the Alarm to silence the unit for 10 minutes If when the Alarm sounds there is no sign of smoke he...

Страница 5: ...ach children how to escape open windows and use roll up fire ladders and stools without adult help Make sure they know what to do if the alarm sounds 1 Check room doors for heat or smoke Do not open a...

Страница 6: ...er this Smoke Heat Alarms don t last indefinitely For example if there is a build up of contamination performance will be impaired It is recommended that the Smoke Heat Alarms are replaced after 10 ye...

Страница 7: ...the red light flashing the others are probably satisfactory 2 LOW BATTERY OTHER BEEPS Check the green mains power light is on If not check fuse circuit breakers and wiring connections If the green li...

Страница 8: ...Australia PTY Ltd 4 Pike Street Rydalmere NSW 2116 Australia Tel 0296841466 www brooks com au Ei Electronics Shannon Co Clare Ireland Tel 061 471277 www eielectronics com Contact Us Certified To AS37...

Страница 9: ...ES SLIDE ON ALARM 3 LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW INSERT A FLAT BLADED SCREWDRIVER HORIZONTALLY APPROX 1cm INTO THE CENTRE OF THE REMOVAL...

Страница 10: ...oughout the house particularly in the bedrooms It is also important that nuisance false alarms are minimised to ensure the units are not disabled or ignored The Australian Standard AS1670 1 gives guid...

Страница 11: ...ceptable that a warning will only be given by the Heat Alarm when there is a very significant flaming fire in the room If the door s and windows are not closed to contain the fire and heat it is extre...

Страница 12: ...ly be considered where close spaced beams or similar obstructions may preclude ceiling mounting It is considered to be the responsibility of the installer client to determine if the presence of asbest...

Страница 13: ...ilt in terminal block to connect it to the mains The mounting plate can be screwed directly to the ceiling Alternatively it can be screwed to a junction box It requires a current of 50mA The Alarm mus...

Страница 14: ...blue or marked N See page 16 for information on interconnection Note Wiring must be installed in compliance with AS3000 Warning Mixing the Live and Neutral connections when interconnecting Alarms will...

Страница 15: ...t seals around the edge of the hole in the ceiling or wall This is to prevent air draughts affecting the smoke heat entering the Alarm If the hole is too large or the Alarm does not seal it it should...

Страница 16: ...e units with red light flashing rapidly which are causing all the other Alarms to sound WARNING Do not connect these Alarms to any other model produced by another manufacturer Doing so may damage the...

Отзывы: