background image

Interconnecting Alarms

Note:

 A maximum of twelve EIB161e / EIB164e / 

EIB166e / EIB166e DHHS Smoke or Heat Alarms may 

be interconnected. Up to 8 additional accessories may 

also be connected.

If you wish to connect more than 12 Alarms contact your 

local distributor.

Systems using more than 3 or 4 Alarms must be very 

carefully planned to ensure nuisance/false alarms are 

not excessive. e.g. from cooking fumes or steam. The 

following is suggested:
• An Alarm Control Switch should be incorporated into 

the system and be readily accessible to all occupants 

so that the source of an alarm can be quickly identified.

• All Alarms must be cleaned and maintained regularly.
• A qualified person must be on call to quickly remove 

any nuisance units (i.e. units with red light flashing 

rapidly) which are causing all the other Alarms to 

sound.

WARNING:

 Do not connect these Alarms to any 

other model produced by another manufacturer. 

Doing so may damage the Alarms and could result in 

a shock or fire hazard.

Wiring must be installed in compliance with AS3000.

230V supply  

Brown, red or marked L

Neutral    

Blue, black or marked N

Interconnect  

Connect to the third core

The interconnect wire (minimum 0.75mm

2

 cable) must 

be  treated as if it was Live. It should be insulated and 

sheathed.
A maximum of 250 metres of wire can be used (maximum 

resistance between detectors 50 Ohms).
These Smoke/Heat Alarms should be interconnected 

only within the confines of a single family living unit. If 

they are connected between different units there may be 

excessive nuisance/false alarms. Everybody may not be 

aware that they are being tested or that it is a nuisance/

false alarm caused by cooking etc.

16

Содержание BROOKS EIB160e Series

Страница 1: ...interconnected Please contact your local distributor for more information Interconnection can be achieved by hardwire or through a modular RF module the EIB100MRF which can be inserted into the base o...

Страница 2: ...nds The cause of the alarm should be investigated After 24 hours the memory will be cleared 3 Press the test button for up to 10 seconds to ensure the sensor chamber electronics and sounder are workin...

Страница 3: ...g left without mains power for long periods the Smoke Heat Alarms should be removed from their mounting plates to prevent the batteries becoming fully depleted This is sometimes done with holiday home...

Страница 4: ...type When sure that it is just a nuisance false alarm simply press the test silence button briefly on the Alarm to silence the unit for 10 minutes If when the Alarm sounds there is no sign of smoke he...

Страница 5: ...ach children how to escape open windows and use roll up fire ladders and stools without adult help Make sure they know what to do if the alarm sounds 1 Check room doors for heat or smoke Do not open a...

Страница 6: ...er this Smoke Heat Alarms don t last indefinitely For example if there is a build up of contamination performance will be impaired It is recommended that the Smoke Heat Alarms are replaced after 10 ye...

Страница 7: ...the red light flashing the others are probably satisfactory 2 LOW BATTERY OTHER BEEPS Check the green mains power light is on If not check fuse circuit breakers and wiring connections If the green li...

Страница 8: ...Australia PTY Ltd 4 Pike Street Rydalmere NSW 2116 Australia Tel 0296841466 www brooks com au Ei Electronics Shannon Co Clare Ireland Tel 061 471277 www eielectronics com Contact Us Certified To AS37...

Страница 9: ...ES SLIDE ON ALARM 3 LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW INSERT A FLAT BLADED SCREWDRIVER HORIZONTALLY APPROX 1cm INTO THE CENTRE OF THE REMOVAL...

Страница 10: ...oughout the house particularly in the bedrooms It is also important that nuisance false alarms are minimised to ensure the units are not disabled or ignored The Australian Standard AS1670 1 gives guid...

Страница 11: ...ceptable that a warning will only be given by the Heat Alarm when there is a very significant flaming fire in the room If the door s and windows are not closed to contain the fire and heat it is extre...

Страница 12: ...ly be considered where close spaced beams or similar obstructions may preclude ceiling mounting It is considered to be the responsibility of the installer client to determine if the presence of asbest...

Страница 13: ...ilt in terminal block to connect it to the mains The mounting plate can be screwed directly to the ceiling Alternatively it can be screwed to a junction box It requires a current of 50mA The Alarm mus...

Страница 14: ...blue or marked N See page 16 for information on interconnection Note Wiring must be installed in compliance with AS3000 Warning Mixing the Live and Neutral connections when interconnecting Alarms will...

Страница 15: ...t seals around the edge of the hole in the ceiling or wall This is to prevent air draughts affecting the smoke heat entering the Alarm If the hole is too large or the Alarm does not seal it it should...

Страница 16: ...e units with red light flashing rapidly which are causing all the other Alarms to sound WARNING Do not connect these Alarms to any other model produced by another manufacturer Doing so may damage the...

Отзывы: