background image

Installation Instructions

DS240 and DS241

Long Range Beam Smoke Detectors

1.0

Description

The DS240 and DS241 are long range projected beam type smoke
detectors which consist of a separate transmitter and receiver.  Internal
pointability provides coverage flexibility without the need for brackets.
Automatic Signal Synchronization and Range Adjustment reduce
installation costs. Selectable sensitivity and alarm response time
provide installation flexibility.

2.0

Specifications

• Operating Voltage: DS240: 18.0 VDC to 32.0 VDC

DS241: 10.2 VDC to 15.0 VDC

•  Standby Current:

DS240: Receiver: 45 mA @ 24.0  VDC

Transmitter: 20 mA @ 24.0  VDC

DS241: Receiver: 50 mA @ 12.0  VDC

Transmitter: 20 mA @ 12.0  VDC

• Receiver Alarm

Current:

DS240: 60 mA @ 24.0  VDC
DS241: 75 mA @ 12.0  VDC

• Range  (distance

between transmitter
and receiver):

30 ft to 350 ft (9 m to 107 m)

• Spacing (distance

between systems): Allow no more than 60 ft (18 m) between

systems. Sixty foot spacing is confirmed
by Underwriters Laboratories, Inc. testing.

• Pointability:

Internally pointable optics for ±90°
horizontal, and ±10° vertical adjustment.

• Sensitivity:

Field selectable for 20, 30, 40, 50, 60, or
70 percent beam obscuration.

• Alarm Contacts:

Normally Open contacts rated 1 A,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.

• Trouble Contacts:

Normally Closed contacts rated 1 A, 60 VDC
maximum for DC resistive loads.  Do not
use with capacitive or inductive loads.

• Aux. Alarm

Contacts:

Form "C" (NO, C, NC) contacts rated 1 A,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.

• Tamper:

Receiver:

Access door tamper switch in
series with trouble contacts.

Transmitter: Upon cover’s removal, cover

tamper switch interrupts
transmission.

• System Signaling:

Conventional 4-wire system. Not for use
with systems that incorporate an alarm
verification feature.

• Signal Delay:

Fire:

Selectable 30 sec or 5 sec

Trouble:

20 ± 2 sec

• Temperature:

The storage and operating temperature
range is -22°F to +130°F (-30°C to +54°C).
For UL Listed installations, the range is
+32°F to +130°F (0°C to +54°C).

• Mounting:

The units are designed to be mounted to
4 in. (10 cm) square or octagonal
electrical boxes (not supplied).

• Listings and

Approvals:

UL

S3019

ULC

CS692

MSFM

Permit #1943

NY City MEA

Acceptance #MEA274-93-E

CSFM

#7260-1062:106

FM

Job #OX2A9.AY

• Standard

Accessories:

DIS2000 Remote Test/Indicator Plate and
Test Cable

• Options:

DIS240 Remote Indicator Plate, TK240
Field Test Kit, AL240 Alignment Light, and
TC2000 Test Cord.

3.0

Principle of Operation

Each DS240 or DS241 beam smoke detector has a separate
transmitter and receiver. The transmitter transmits an invisible infrared
beam of a specific frequency and intensity. The receiver detects, then
measures the beam’s intensity (see 

Figure 1).

Figure 1 - Infrared Transmission

As the beam is obscured by smoke, the receiver senses a decrease
in the signal strength and measures that decrease. The receiver
compares the signal level with two preset thresholds: an alarm
threshold which is set using the sensitivity switch and a trouble
threshold which is preset at approximately 10%. If the signal falls
below the alarm threshold for the programmed alarm period, the
receiver signals an alarm (see 

Figure 2).

Figure 2 - Beam Obscuration

If the signal falls below the trouble threshold for more than 20 sec,
such as might happen if the beam is blocked by a foreign object, the
receiver signals a trouble condition (see 

Figure 3).

Figure 3 - Beam Blockage

The receiver automatically compensates for the gradual loss of signal
due to dust/dirt build-up on the cover. After 50 percent of the signal is
lost, the receiver will indicate a trouble. When the dust/dirt build-up is
cleaned or the blockage is removed, the detector automatically goes
back to its normal operation level.

A trouble will be indicated at the receiver if the beam strength is
increased by more than 20% for greater than 20 sec. Causes include
improper initial alignment or the removal of a partial beam blockage
at the time of alignment. Preform a fine-tune alignment (see 

Section

7.3 Fine Tune Alignment on page 6).

Downloaded from:

 http://www.guardianalarms.net

Содержание DS240

Страница 1: ...s 22 F to 130 F 30 C to 54 C For UL Listed installations the range is 32 F to 130 F 0 C to 54 C Mounting The units are designed to be mounted to 4 in 10 cm square or octagonal electrical boxes not supplied Listings and Approvals UL S3019 ULC CS692 MSFM Permit 1943 NY City MEA Acceptance MEA274 93 E CSFM 7260 1062 106 FM Job OX2A9 AY Standard Accessories DIS2000 Remote Test Indicator Plate and Test...

Страница 2: ...ose to the beam path can cause the beam to become distorted You can test for beam distortion by monitoring the signal voltage After setup the signal voltage of the detector should read 4 VDC Monitor the voltage and turn on all heating and cooling devices in the area The signal voltage should not fluctuate more than 0 20 VDC If it does the detector should be moved to avoid these disturbances 4 2 Av...

Страница 3: ... the top edges of the mounting box Over tightening the mounting screws bows the mounting plate inward at the bottom causing the optics to aim low Irregularities in the flatness of the mounting box edge surfaces or screw tabs will worsen this condition Using only mounting boxes with flat regular surfaces and properly formed screw tabs and tightening the mounting screws to secure the mounting plate ...

Страница 4: ...ide a means of checking the condition of the detector from ground level If a DIS2000 or DIS240 Remote Indicator Plate will be used install the Remote Indicator Connector to the receiver now see Figure 7 NOTE The DIS240 remote indicator should be located no further than 100 ft 31 m from the receiver and wired with 18 AWG 1 2 mm or larger wire The DIS2000 may be wired up to 500 ft 152 m from the rec...

Страница 5: ...e tune the image to the center of the mirror in line with the front and rear bore sights Replace and secure the transmitter s cover when this alignment procedure is complete Check the transmitter s green LED It should be flashing Replace and secure the transmitter s access door Align the receiver to the image of the transmitter using the above preliminary alignment procedure Check the receiver s g...

Страница 6: ...rough the opening in the cover red lead towards center of unit An alarm test may be performed here if desired by connecting the white and black wires of the TC2000 To reset the unit temporarily remove power Press the receiver s Set up button located just below the P6 test cable connection see Figure 15 Press only if the covers are on both transmitter and receiver This starts a one to two minute au...

Страница 7: ...by setting the Sensitivity Pot Setting as recommended in Section 7 2 Sensitivity Adjustment on page 5 Since the total obscuration of the beam by smoke increases with distance between the units because more smoke will be within the beam path the detector can be made less sensitive as the distance increases Additionally the sensitivity of the detector should be made less at greater distances because...

Страница 8: ...esidential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in strict accordance with the manufacturer s instructions and recommendations may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to...

Страница 9: ...DS240 DS241 Installation Instructions 2004 Bosch P N 22066P Page 9 9 0 Troubleshooting ...

Страница 10: ...Page 10 P N 22066P 2004 Bosch DS240 DS241 Installation Instructions 10 0 Installing Multiple Units ...

Страница 11: ...DS240 DS241 Installation Instructions 2004 Bosch P N 22066P Page 11 11 0 Quick Start Installation Flow Chart ...

Страница 12: ...osch 22066P 7 04 130 Perinton Parkway Fairport NY 14450 9199 USA Installation Instructions DS240 DS241 Long Range Beam Smoke Detectors Customer Service 800 289 0096 Technical Support 888 886 6189 Page 12 of 12 ...

Отзывы: