11
System Details
EHC
System Details
5.
Operation Modes
5.1
Circuit for CH (central heating) mode
When central heating is in demand, the three-way valve
1.
is set to CH mode position.
When the burner has ignited and the flame is detected,
2.
the control starts heating up the CH water to the set
temperature. This control regulates the gas input rate by
changing the fan speed.
The pump runs from 0 to 600 seconds depending on the
set temperature.
Blow Fan
Circulation
Pump
Gas Valve
Ignition
Electrode
Flame Sensing
Electrode
Metal Fibre
Burner
Expansion
Vessel
Three-way
Valve
Heat
Exchanger
Gas
Inlet
Mixing Flow
Guide
CH
Flow
CH
Return
Note
Low water pressure error
cancelling function
If the water pressure falls below 0.4 bar, the low
water pressure error occurs on the control panel.
Note
Weather Compensation
If an outdoor temperature probe is connected,
the weather compensation function can be used.
With this function, the target primary temperature
is automatically set according to the outdoor
temperature (K-factor).
Note - The control panel enables you to adjust
the parameters by resetting the K-factor.
K=0.5
K=1
K=1.5
K=6
K=4
K=3
K=2
20
20.0
30.0
40.0
50.0
60.0
70.0
80.0
15
10
5
0
-5
-10
-15
-20
-25
Outdoor Temperature (°C)
Ta
rget primar
y t
emperatur
e
3.
Relationship between primary and outdoor temperature: K-factor
In this event re-pressurise the boiler to 1.5 bar
Note
The minimum operating
pressure can be adjusted in the
service menu.