background image

4

Wooden boards 

Any loose boards should be properly screwed down. A specially designed insulating underlay is recommended to improve 
soundproofing (see section 

Attention!

 Underlay materials). A moisture protection film (vapour barrier) is not necessary. The 

laminate flooring boards must be laid at right angles to existing floorboards.

Elastic flooring surfaces (PVC, linoleum, vinyl)

The use of flexible floor coverings meets the damp-proofing requirements and thus eradicates the need for a moisture protection 
film. A specially designed insulating underlay is used to improve soundproofing (see section: 

Attention!

 Underlay materials).

Wet rooms / wet areas

Attention!

 Laminate flooring from EGGER is not suitable for installations in wet rooms and wet areas such as bathrooms, saunas or 

in similar rooms. In case of failure to comply, all guarantee and warranty claims will become void.

Attention! Underlay materials

 

ƒ

On mineral sub-surfaces, however, a moisture protection film with an SD value ≥ 75 m must always be installed first, over 
the entire surface and extend up the walls. Exceptions are the use of EGGER Silenzio Duo (2 in 1 insulation underlay with 
integrated moisture protection) or a comparable 2 in 1 underlayer board. In these cases, a separate moisture protection 
film is not necessary.

 

ƒ

A system-specific EGGER Silenzio underlay must be used under EGGER laminate flooring. Alternative underlayer boards are 
available at 

www.egger.com

. The exception is the EGGER laminate flooring with laminated Silenzio underlayer board on the 

reverse. An additional insulation underlay is not permitted in this case. 

3. Before the installation

Acclimatisation of the floor boards

The packages of laminate flooring have to be stored in the room where they will be installed or in a room with the same climate 
condition before starting the installation. Acclimatisation takes place within the following guidelines:

 

ƒ

packed

 

ƒ

for a period of at least 48 hours

 

ƒ

laid flat with a minimum of 50 cm from all walls

 

ƒ

at a room temperature of at least 18° C

 

ƒ

at a flooring surface temperature of at least 15° C

 

ƒ

at a relative atmospheric humidity of between 40 % and 70 %

Direction of installation

Laminate flooring looks best when the floor boards are installed parallel to the light direction. However, in the case of sub-floors 
made of floorboards or strip parquet / wooden floors, the floorboards must be installed at right angles or in the same direction of 
the strip parquet / wooden floor.

Planning the first row

First, the room must be measured to determine whether the width of the first row should be reduced. This will be necessary if the 
last row to be laid is calculated to be less than 5 cm wide.

Planning expansion gaps

Laminate flooring, like all organic materials, is subject to certain types of movement (shrinkage / expansion) due to changes in 
climate conditions. If expansion joints are used, the installed floor will not be affected as they provide spaces for these changes 
to take place. Expansion gaps 8 to 10 mm wide to all fixed objects such as walls, door frames, pipes, pillars, stairs etc. should be 
observed.

Installation sub-floors/Prior to installation

Содержание JUSTclic!

Страница 1: ...Installation instructions Egger Laminate Flooring with JUSTclic installation system...

Страница 2: ...e of fast setting screed the measurements and limitis specified by the respective manufacturer shall apply The test material must be obtained from the lower one third of the screed During this process...

Страница 3: ...cting the function of the floor heating cooling system functional heating cooling Proof of the proper raising and lowering of the temperature of the heated screed structure in any season must be provi...

Страница 4: ...nate flooring with laminated Silenzio underlayer board on the reverse An additional insulation underlay is not permitted in this case 3 Before the installation Acclimatisation of the floor boards The...

Страница 5: ...observing the required gaps placing the spacers Figure 3 to 10 Start installing the 2nd row with the remaining panel of the 1st row if the latter is at least 200 mm long In the following rows the new...

Страница 6: ...to the top of the tongue on the short and long edge The glue should ooze out along the complete long and short edge after the panels have been connected together Excess sealing glue is easy to remove...

Страница 7: ...an then be pushed horizontally over the groove of the previously installed panel This connection area has to be glued with a PVAC glue If you have a door frame that cannot be shortened e g one made of...

Страница 8: ...exception of Aqua Laminate Flooring Only clean the laminate floor with a damp cloth Never use abrasives or scouring agents on the laminate floor Do not use cleaning products that may leave a residue...

Страница 9: ...41 301 20222 flooring egger com EGGER Drevprodukt Gagarin Ezhvinsky proezd 1 215010 Gagarin Oblast Smolensk Russia T 7 48135 79 300 F 7 48135 79 311 info ru egger com BR_flo_EGGER_installation_instruc...

Отзывы: