Troubleshooting
Problem
Possible errors
Action
The fan will not start
- The fan is turned off
- Boiler overhetaed
- Faulty start capacitor
- Faulty fan motor
- Press start new firing
- Reset overheat protection
- Contact installer
- Replace the fan
Smoke is seeping through the doors.
- Leaking gasket
- Adjust the doors
White smoke from the chimney
- Low flue gas temperature
- Too big chimney
- Rain water in the chimney
- Cut turbulators/increase effect
- Contact installer
- Mount a rain hood
Black smoke from the chimney,
poor combustion
- Moist wood
- Sooty boiler
- Change wood
- Clean according to manual
Boiler overheated
- Air in the system
- Too large insert of wood
- Bleed the system
- Adjust amount of wood
Tar in the convection section.
- A sooty loading compartment
- Sooty combustion plate
- Moist wood
- Leaking gasket
- Clean loading compartment
- Clean combustion plate
- Fire with dry wood
- Check for leakage in the gaskets
Little or no heat is transferred to the
accumulator tank.
- Air in the system
- Moist wood
- Refill the system thoroughly
- Use more dry wood, or finely chopped
The boiler has a low output and is sluggish.
- Moist wood
- The boiler may need a cleaning
- Use more dry wood
- Clean the boiler
The loading pump creaks or thumps,
- Probably air in the system
- Low system pressure
- Follow the instructions for Laddomat
- Increase the pressure
The pressure drops in the system.
- There is a leakage in the system
- Wrong first pressure in the pressure vessel
- Fill with water and bleed
- Adjust the pressure
Noise from the fan.
- The cooling wing scrapes against the boiler.
- The bearings in the fan have run out.
- Check the cooling wing
- Change the fan
High flue gas temperature.
- Soot in the tubes in the convection
- Clean the tubes
No heat on radiators
(only if shunt is controlled from the boiler)
- Shunt motor closed
- Shunt motor is broken
- Radiator pump is not activated
- Radiator pump is broken
- Air in the radiator circuit
- Contact installer
- Contact installer
- Activate in the shunt control
- Contact installer
- Bleed the circuit
A sensor shows wrong temperature
- Faulty sensor
- Calibrate
- Change sensor
- Cal/- in the menu "Other"
Incorrect lambda value
- Dirty lambda probe
- Faulty lambda probe
- Clean the probe
- Change the lambda probe