EFD ValveMate 7040 Скачать руководство пользователя страница 8

Initiate Connection

The 7040 can be operated by
applying a 5 to 24 VDC pulse to
terminal pins 1 and 2, or providing
contact closure across pins 5 and
7. Alternatively, a foot pedal may
be ordered (#2015A) and plugged
into the connector located on the
rear panel.

Air Input Connection

1. Connect the controller to plant air

by first installing the five micron
filter regulator (#2000F755) to
the plant air supply.

2. Install the air tee with barb fit-

ting (#1116 supplied with EFD
tank reservoirs) in the output of
the filter regulator, and install the
black hose with coupling to the
barb fitting. The quick-connect
on the air tee is used to provide
air pressure to the air pressure
regulator on EFD tank reser-
voirs. This connection will be
made during valve installation.

3. Remove the cap plug from the air

input of the controller and attach
the input air hose coupling onto
the controller air-input fitting. 

4. Set the pressure at the filter 

regulator to 70 psi (4.8 bar).

➄ 

Control Air Output

The 781S is equipped with nozzle
and control air hoses with male
quick-connects that plug into the
ValveMate 7040.

a) Plug the control air hose

labeled “A” into output “A”
(white) of the 7040. 

b) Plug the nozzle air hose

labeled “B” into output “B”
(black).

➅ 

Power

1. Turn the power switch on.

2. Press the time override button

to place the controller in manual
mode (---).

Output A

Output B

120

6 / Setup

a

b

Setup

Содержание ValveMate 7040

Страница 1: ...VALVEMATE 7040 Electronic pdf files of EFD manuals are also available at www efd inc com manuals html ValveMate 7040 Controller Operating Manual A NORDSON COMPANY...

Страница 2: ...y exceed the purchase price of the equipment This warranty is valid only when oil free clean dry filtered air is used EFD makes no warranty of merchantability or fitness for a particular purpose In no...

Страница 3: ...ions 2 Operating Features 3 Typical Setup 4 Setup 5 6 Adjusting the Spray 7 Programming Nozzle Air Delay 8 Schematic and Replacement Parts 9 Troubleshooting Guide 10 Input Output Connections 11 12 Con...

Страница 4: ...kg 3 1 lb Cabinet Aluminum Input Voltage Selectable 100 120 220 VAC Internal Voltage 24 VDC Feedback Circuits 5 to 24 VDC NC solid state switch 250mA maximum Initiate Circuit 5 to 24 VDC signal or con...

Страница 5: ...999 to 9 99 or 99 9 Decimal does not appear in the display while in the 999 second range Operating Features 4 Program Press to clear display to zeros Display flashes bright dim while in program mode P...

Страница 6: ...es fail safe air pressure release during cap removal Typical Setup 7543BP for 1 4 OD tube 7610BP for 3 8 OD tube LVLP spray valve Plant air 70 psi 4 8 bar minimum Material Constant air Pulsed air for...

Страница 7: ...00PMK Input Power 1 View cartridge window in power cord receptacle to ensure that the voltage is set properly Selections are 100 120 or 220 VAC 2 If it does not match remove the fuse cartridge Then re...

Страница 8: ...ng The quick connect on the air tee is used to provide air pressure to the air pressure regulator on EFD tank reser voirs This connection will be made during valve installation 3 Remove the cap plug f...

Страница 9: ...ntrol knob and or tank air pressure Note Avoid tight stroke settings with high tank pressure 4 To change nozzle air use the nozzle air pressure regulator Higher pressures will provide finer spray To M...

Страница 10: ...power switch on 3 The display will read SEL select Release the time override button 4 Press either the up or down time set buttons once and release The current nozzle air delay setting will be display...

Страница 11: ...ly 7 2001A Gauge 0 to 30 psi 0 to 2 07 bar 8 2004B Female quick connect black hidden from view below item 9 9 2004B W Female quick connect white 10 2024 160 1 4 OD x 160 ID tubing 11 2081A Air input q...

Страница 12: ...input voltage Ensure that the external voltage to the circuit is between 5 and 24 VDC and that the load does not exceed 250mA If the circuit has been overloaded the fuse may have blown Replace fuse i...

Страница 13: ...le an open collector circuit closes and remains closed until the next dispense cycle This circuit can be utilized to signal back to a host computer start another device in sequence or other operations...

Страница 14: ...12 VA 5 VDC Solenoid 1 7815 control Protector Solenoid 2 atomizer control Power supply Nonvolatile memory Programmable display Opto coupler 24 VDC Mechanical Contact Initiate Mechanical contact power...

Страница 15: ...h each controller that is connected The initiate power supply should be sized accordingly 2 End of Cycle Feedback Circuit This circuit will ensure that the end of cycle signal will come from the last...

Отзывы: