background image

2) PLUMBING HOOK-UP

1) The unit is supplied with compression fittings. USE THESE: DO NOT
USE THREADED PIPE FITTINGS. DO NOT USE PIPE DOPE
OR TEFLON TAPE ON THIS INSTALLATION. Ensure the inlet filter supplied
with this unit is in place.

2) Take care to ensure that the pipes are correctly aligned with the inlet and
outlet bosses in order to avoid excessive stress on the heater body molding.

NOTE: Run water through the supply pipe to remove all debris from the
pipe before connecting the heater. Failure to do so could damage the flow
switch.

3) Install isolating valves (full flow ball valve type) on both inlet and outlet
pipes. This allows unit to be isolated for maintenance purposes. (Fig. 2)

4) When all plumbing is complete, fully check the system for water leaks
at all plumbing connections. If leak is present take corrective action. If leak
is at the compression fitting, slowly tighten compression nut until it stops.
Ensure compression fittings are tighten to 18FT.LB.
Fully open both inlet and outlet ball valves.
Run all hot water outlets fed by this heater one at a time for a minute or two 
until the water flow is continuous, free from “gulping” and from all visible air

4) COMMISSIONING YOUR HEATER

IMPORTANT

Before switching “on” the power at the breaker make sure that the hot

water circuit is free of air pockets or premature failure of the heating element will occur.

To do this open all hot water faucets one at a time for a minute or two until the water flow

is continuous and free from “gulping” and from visible air pockets.

1) With inlet and outlet BALL VALVES fully open, turn on all hot water outlets.

2) Run for 5 minutes, turning faucet “on” and “off” repeatedly.

3) Switch on electric supply at breaker.

4) The power indicator light should now come on (see Fig. 1). 

NOTE: At this point water temperature may not be very hot.

5) Using the OUTLET BALL VALVE slowly reduce water flow until desired

temperature is achieved at hot water outlet.

NOTE: The water temperature is proportional to the flow  through the heater. 

until the water flow is continuous, free from “gulping” and from all visible air
pockets.

NOTE:

ALL PLUMBING MUST BE COMPLETED BEFORE YOU

PROCEED WITH THE ELECTRICAL HOOK-UP.

TEST THE INSTALLATION FOR LEAKS BEFORE

CONNECTING THE ELECTRICAL SUPPLY.

NOTE: The water temperature is proportional to the flow  through the heater. 
The lower the flow  the higher the temperature and vice versa

.

6) Check performance of flow switch by opening and closing outlet valve a few  times.

The power indicator light should be on 

ONLY

when water is flowing through the unit. 

For expected temperature rise at various rates of flow see chart.

NOTE: An SP55 (5.5 kW) unit at 240 V will deliver 0.5 gallon per minute at 75

o

F

temperature rise. For example, with incoming water temperature at 45

o

F the

unit will produce 0.5 gallon per minute at (45+75)=120

o

F.

7) It is possible that drawing off cold water at comparatively high rates of flow

elsewhere in the building at the same time that the heater is working, could 
cause premature element failure. Care should be taken not to starve the unit 
of cold water. To prevent this from happening, open fully the main valve on 
the cold supply to the building and throttle back the control valves to the other 
cold water outlets. 

Hot outlet
compression 
fitting
DO NOT
SOLDER

Fig 1

Note: “Single Point” units comes with a faucet mounted aerators, these should
be mounted on the faucets served by this unit. 

Cold inlet 
Compression 
FITTING
DO NOT
SOLDER

Inlet 
filter 
screen

Содержание Single Point Series

Страница 1: ...ATSOEVER THE MANUFACTURER OF THIS HEATER WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING INSTRUCTIONS OUTLINED ON THE FOLLOWING PAGES Eemax Inc 353 Christian Street Oxford CT 06478 THE INSTALLATION MUST CONFORM WITH THE INSTRUCTIONS IN THIS MANUAL AND LOCAL CODES OR INTHE ABSENCE OF LOCAL CODES WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL C...

Страница 2: ...plastic piping Do not use additional screwed fittings or pipe dope Doing so will void the warranty DO NOT SOLDER PIPES WHILE THE UNIT IS INSTALLED DO NOT USE PIPE DOPE OR TEFLON TAPE serious damage to the electronic flow switch will result position WILL cause element burn out 3 The cold water inlet is on the right hand side and the hot water outlet is on the left hand side Under NO circumstances c...

Страница 3: ...ucet on and off repeatedly 3 Switch on electric supply at breaker 4 The power indicator light should now come on see Fig 1 NOTE At this point water temperature may not be very hot 5 Using the OUTLET BALL VALVE slowly reduce water flow until desired temperature is achieved at hot water outlet NOTE The water temperature is proportional to the flow through the heater until the water flow is continuou...

Страница 4: ... OUTS INLET VALVE A FULLY OPEN The heaters are rated at 240 Volts If the actual voltage supplied is lower 220 208V there will be a proportional drop in output 1 Wire entry into the unit should be made through the lower right hand corner of the backplate via one of the two knockout holes provided 2 The mains wires should be connected to the slots in the terminal block marked L1 and L2 or N The grou...

Отзывы: