P/N 387040P-
EN • REV 013 • ISS 20SEP17
5 / 5
Specifications
Operating voltage range
15.20 to 19.95 VDC
Current
Standby
Activated
310 µA
135 µA
Maximum line impedance
Refer to the control panel installation
manual
Ground fault impedance
10 kΩ
Output ratings
(special applications)
24 VDC
25 VRMS audio
70 VRMS audio
EOL resistor value
Circuit resistance
Circuit capacitance
2 A
50 W
35 W
47 kΩ, UL/ULC Listed
Refer to the control panel installation
manual
0.1 µF max.
UL/ULC Listed EOLR
47 kΩ (P/N EOL-47)
Circuit designation
Signaling line circuits
Notification line circuits
Class A, Style 6 or Class B, Style 4
Class B, Style Y
LPCB/CPR electrical box
Requirements
Minimum size W × H × D
Plastic box with cover plate, no gaps
or unused holes
3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm)
Compatible electrical boxes
2-1/2 in. (64 mm) deep dual-gang box;
4 in. square box
1-1/2 in. (38 mm) deep box with a
dual-gang cover
Wire size
12 to 18 AWG (1.0 to 4.0 mm²)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93%, noncondensing
Storage temperature range
−4 to 140°F (−20 to 60°C)
Regulatory information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired operation.
North American
standards
CAN/ULC-S527, UL 864
EN 54
EN 54-18: 2005 Input/output devices
EU compliance
CPR certificates
0832-CPR-F0329
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information, see:
www.recyclethis.info.