Specifications 

 

Operating voltage range 

15.20 to 19.95 VDC 

Current 
 

Standby 

 

Activated 

 
310 µA 
135 µA 

Maximum line impedance 

Refer to the control panel installation 
manual 

Ground fault impedance 

10 kΩ 

Output ratings  
(special applications) 
 

24 VDC 

 

25 VRMS audio 

 

70 VRMS audio 

 

EOL resistor value 

 

Circuit resistance  

 
 

Circuit capacitance 

 
 
2 A 
50 W 
35 W 
47 kΩ, UL/ULC Listed 
Refer to the control panel installation 
manual 
0.1 µF max. 

UL/ULC Listed EOLR 

47 kΩ (P/N EOL-47) 

Circuit designation 
 

Signaling line circuits

 

Notification line circuits 

 
Class A, Style 6 or Class B, Style 4 
Class B, Style Y  

LPCB/CPR electrical box 

Requirements 
 
Minimum size W × H × D 

 
Plastic box with cover plate, no gaps 
or unused holes 
3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep dual-gang box; 
4 in. square box  
1-1/2 in. (38 mm) deep box with a 
dual-gang cover 

Wire size 

12 to 18 AWG (1.0 to 4.0 mm²) 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93%, noncondensing 

Storage temperature range 

−4 to 140°F (−20 to 60°C) 

Regulatory information 

 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause 
harmful interference, and (2) this device must 
accept any interference received, including 
interference that may cause undesired operation. 

North American 
standards 

CAN/ULC-S527, UL 864 

EN 54 

EN 54-18: 2005 Input/output devices 

EU compliance

 

 

CPR certificates 

0832-CPR-F0329 

 

2002/96/EC (WEEE directive): Products marked 
with this symbol cannot be disposed of as 
unsorted municipal waste in the European Union. 
For proper recycling, return this product to your 
local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated 
collection points. For more information, see: 
www.recyclethis.info. 

Contact information 

For contact information, see www.edwardsfiresafety.com. 

 

 

Содержание SIGA-CC2

Страница 1: ...s described below to configure the SIGA CC2 module See Table 1 for listing information Table 1 Personality codes Code Description UL 864 CAN ULC S527 EN 54 18 7 Riser selector supervised output Class B Personality code 7 Riser selector supervised output Class B Configures the SIGA CC2 module as a one or two input signal power 24 VDC or audio evacuation 25 or 70 VRMS riser selector The output circu...

Страница 2: ...ations Each terminal on the module is limited to a single conductor Test resistors are supplied with the SIGA CC2 to prevent trouble signals on unused circuits during installation When connecting field wires remove the test resistors and install a UL ULC Listed 47 kΩEOLR at the end of the circuit The module does not support conventional smoke detectors Riser wiring notes For maximum line impedance...

Страница 3: ...conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 If using a G1 P Genesis series horn while connected to a compatible fire alarm control panel a CDR 3 Bell Coder must be used to comply with NFPA 72 standard alarm ev...

Страница 4: ...tted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Unshielded twisted pair 5 47 kΩ EOLR P N EOL 47 6 Signaling line circuit SLC to next device 7 Channel 1 ALE...

Страница 5: ...x with a dual gang cover Wire size 12 to 18 AWG 1 0 to 4 0 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory information FCC compliance This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and...

Отзывы: