background image

 

2 / 5 

 

P/N 387040P-

EN • REV 013 • ISS 20SEP17 

Figure 1: Installing the SIGA-CC2 module 

 

(1)  Compatible electrical box 
(3)  SIGA-CC2 module 
(3)  Wall plate 

(5)  #6-32 × 5/8 machine screw 

(4X) 

(6)  #4 × 1/2 self-tapping screw  

Protection from transient spikes 

For installations in which the output circuit connects to 
electromechanical bells or horns, install a bipolar transient 
protector (P/N 235196P) to protect the module from transient 
spikes caused by switching inductive loads. Locate bells and 
horns at least 6 ft. (1.8 m) from the module. 

To install a bipolar transient protector: 

1.  Install the transient protector across the output circuit 

inside the electrical box with the module. See Figure 2. 

Figure 2: Bell circuit showing bipolar transient protector 
placement 

 

(1)  Normal state 

(2)  Active state 

 

 

 

 

 

Wiring 

Wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

General wiring notes 

• 

Refer to the Signature loop controller installation sheet for 
SLC wiring specifications.  

• 

Each terminal on the module is limited to a single 
conductor. 

• 

Test resistors are supplied with the SIGA-CC2 to prevent 
trouble signals on unused circuits during installation. 
When connecting field wires, remove the test resistors and 
install a UL/ULC Listed 47 

kΩEOLR at the end of the 

circuit. 

• 

The module does not support conventional smoke 
detectors. 

Riser wiring notes 

• 

For maximum line impedance, refer to the installation 
manual for the fire alarm panel. Maximum circuit 
capacitance is 0.1 µF. 

• 

If the riser is used for more than one notification zone, 
install in accordance with the survivability from attack by 
fire requirements in NFPA 72 

National Fire Alarm and 

Signaling Code. 

• 

The SIGA-CC2 module does not supervise the riser; the 
fire alarm control panel provides this function. 

To wire the module: 

1.  Verify that all field wiring is free of opens, shorts, and 

ground faults. 

2.  Strip 1/4 in. (about 6 mm) from the ends of all wires that 

connect to the terminal block of the module. 

When stripping wire ends, exposing more wire may cause 
a ground fault; exposing less wire may result in a faulty 
connection. 

3.  Connect the field wires. See Figure 3 and Figure 4. 

 

 

 

 

 

 

 

 

(1)

(2)

(3)

(4)

(5)

10

9

(1)

(2)

Содержание SIGA-CC2

Страница 1: ...s described below to configure the SIGA CC2 module See Table 1 for listing information Table 1 Personality codes Code Description UL 864 CAN ULC S527 EN 54 18 7 Riser selector supervised output Class B Personality code 7 Riser selector supervised output Class B Configures the SIGA CC2 module as a one or two input signal power 24 VDC or audio evacuation 25 or 70 VRMS riser selector The output circu...

Страница 2: ...ations Each terminal on the module is limited to a single conductor Test resistors are supplied with the SIGA CC2 to prevent trouble signals on unused circuits during installation When connecting field wires remove the test resistors and install a UL ULC Listed 47 kΩEOLR at the end of the circuit The module does not support conventional smoke detectors Riser wiring notes For maximum line impedance...

Страница 3: ...conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 If using a G1 P Genesis series horn while connected to a compatible fire alarm control panel a CDR 3 Bell Coder must be used to comply with NFPA 72 standard alarm ev...

Страница 4: ...tted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Unshielded twisted pair 5 47 kΩ EOLR P N EOL 47 6 Signaling line circuit SLC to next device 7 Channel 1 ALE...

Страница 5: ...x with a dual gang cover Wire size 12 to 18 AWG 1 0 to 4 0 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory information FCC compliance This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and...

Отзывы: