background image

 

 

 

 

Technical Bulletin  

 

SuperDuct Signature Duct Smoke Detector 

Wiring 

Figure 8 shows how to wire the duct smoke detector and its 
accessories. Run all field wiring into the detector through the 
knockouts located at the top of the detector housing. 

Configuration 

The duct smoke detector is configured at the factory for the 
lowest sensitivity setting and to generate an alarm event when 
activated. Depending on the version of the configuration 
software that you use, you can configure the duct smoke 
detector to generate an alarm event or a supervisory event 
when it is activated.  

Maintenance and service 

Recommended service schedule 

Perform a visual inspection upon installation and once every 
six months thereafter. 

Perform an alarm test upon installation and once every twelve 
months thereafter. 

Testing the duct smoke detector 

Before testing the duct smoke detector, notify the proper 
authorities that the system is undergoing maintenance and, 
unless part of the test, disconnect all auxiliary equipment from 
its common alarm relay contacts. 

Note: 

You can’t initiate an alarm test if the duct smoke 

detector is in the trouble state.  

To test the duct smoke detector’s ability to report an alarm 
condition: 

• 

Using an SD-MAG, hold the SD-MAG where indicated 
on the side of the duct smoke detector for more than 5 
seconds 

• 

Using an SD-TRK, turn the key switch to the TEST 
position for more than 5 seconds 

• 

Using an SD-TRM, hold the SD-MAG test magnet to the 
target area for more than 5 seconds 

Once activated, verify the following: 

• 

The detector’s Alarm LED is flashing 

• 

If connected and configured, the Active LED on the 
remote test station or LED indicator is flashing 

• 

The appropriate event message or visual indication is 
reported on the fire alarm control panel 

After you have finished testing the duct smoke detector, reset 
the control panel in order to restore the detector to its normal 
state. 

Troubleshooting 

The Power LED does not blink 

Check the wiring. Repair or replace any loose or missing 
wiring. 

An internal trouble event message is displayed on the 
control panel 

Check the cover. Make sure it is attached and secured properly 
then reset the control panel. 

Check the detector’s dirty level. Clean if required. See, 
“Cleaning the duct smoke detector.” 

Upload the detector’s trouble table to determine the problem. 
Correct the problem then reset the control panel. 

Note: 

Clearing the trouble message from the panel does not 

remove the trouble from the loop controller’s trouble table. 

Cleaning the duct smoke detector  

Clean the duct smoke detector when it becomes 80% to 99% 
dirty or sooner if conditions warrant. 

Caution: 

Before cleaning the duct smoke detector, notify the 

proper authorities that the fire alarm system is undergoing 
maintenance and take steps to prevent the control panel from 
responding to a false alarm. 

Airflow

HVAC duct

Sampling

tube

Retainer
clip

Optic
plate

Optic
housing

Detector 
housing

 

Figure 6: Detector cleaning diagram 

Содержание 3100738

Страница 1: ...e following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ventilating Systems UL 268A Smoke Detectors for Duct Applications...

Страница 2: ...es are stored in nonvolatile memory This information can be retrieved and reviewed when desired Air is introduced to the duct smoke detector s sensing chamber through a sampling tube that extends into...

Страница 3: ...rm red Power green Common alarm relay Unsupervised and power limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Operating voltage 15 2 to 19 95 Vdc Operating current Standby 45 A Alarm 4...

Страница 4: ...ed when the amount of smoke in its sensing chamber exceeds its alarm threshold setting or when an alarm test is initiated Upon entering the alarm state the duct smoke detector s Alarm LED turns on Com...

Страница 5: ...velocity 2 Drill the mounting holes 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube from the front of the detecto...

Страница 6: ...ion for more than 5 seconds Using an SD TRM hold the SD MAG test magnet to the target area for more than 5 seconds Once activated verify the following The detector s Alarm LED is flashing If connected...

Страница 7: ...oft bristle brush remove loose dirt and debris from inside the detector housing and cover Use isopropyl alcohol and a lint free cloth to remove dirt and other contaminants from the gasket on the detec...

Страница 8: ...uct Signature Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 cm Figu...

Страница 9: ...Active SIGA LED 1 Notes 1 No more than one remote test station or LED indicator can be connected to the detector at the same time Wiring is unsupervised Maximum wire resistance is 10 ohms per wire Pow...

Отзывы: