LSU 110 / 32 - Local Signalization Unit User manual
Operation of DO6:
device without special option (see ordering option 2):
DO6 has device ready function
device with special option 6 (see ordering option 2):
ack. lamp
(2)
DO6
(1)
depends on device setting (see chapter „SETTINGS“)
(2)
button »ACK LAMP« pressed or input »DIB« activated
(3)
button »ACK HORN« pressed or input »DIC« activated
When any binary input is activated, belonging lamp is also activated. Lamp flashing mode
depends on device setting (see chapter „SETTINGS“):
A) when input is activated, lamp lights. When input is deactivated, lamp lights no more, without
any acknowledgement. No DOs are activated.
B) (1. example) when input is activated, lamp start to flash. When input is deactivated, lamp
flashes until lamps are acknowledged (button »ACK LAMP« pressed or input »DIB« activated).
(2. example) when input is activated, lamp start to flash. When lamps are acknowledged (button
»ACK LAMP« pressed or input »DIB« activated) lamp lights until binary input is deactivated.
DO2 normal position is OFF. At activation of any binary input set at B mode, binary output DO2
starts to alternate from OFF to ON position and vice versa. Alternation time depends on lamps
flashing time setting. When lamps are acknowledged (button »ACK LAMP« pressed or input
»DIB« activated), DO2 goes to OFF position no matter of binary input states.
DO3 normal postion is OFF. At activation of any binary input set at B mode, binary output DO3
goes to ON position for 500 ms.
DO4 normal position is OFF. At activation of any binary input set at B mode, binary output DO4
goes to ON position. It stays in that position until horn is acknowledged (button »ACK HORN«
pressed or input »DIC« activated).
DO5 normal postion is OFF. At activation of any binary input set at B mode, binary output DO5
goes to ON position for 500 ms.
3.3 OPERATION DURING TEST
test
DO1
DO2
DO3
DO4
DO5
DO6
When test is activated (button »TEST« pressed or inputs »DIA« activated) all lamps lights.
Binary outputs »DO1« to »DO5« are also activated.
When test is deactivated (button »TEST« not released and inputs »DIA« deactivated) all lamps
start to flash as they were triggered by binary input in normal operation. DOs are set to the
position as they were triggered by binary input in normal operation.