LSU 110 / 32 - Local Signalization Unit User manual
5 IEC 60870-5-103 PROTOCOL
5.1
INFORMATION TABLE
Communication
Protocol
IEC 60870-5-103 (slave)
Supported responds
link reset, class I, class II, general interrogation, time
synhronization (broadcast & single device), general
command
Device address
1 - 255
Station address
1 - 255
Baud rate
19200 (fixed)
Number of data bits
8 (fixed)
Parity
even (fixed)
Number of stop bits
1 (fixed)
Device IEC 60870-5-103 information table
Signal description
Function
Information number GI respond number
digital input 1
240
160
1
digital input 2
240
161
2
digital input 3
240
162
3
digital input 4
240
163
4
digital input 5
240
164
5
digital input 6
240
165
6
digital input 7
240
166
7
digital input 8
240
167
8
digital input 9
240
168
9
digital input 10
240
169
10
digital input 11
240
170
11
digital input 12
240
171
12
digital input 13
240
172
13
digital input 14
240
173
14
digital input 15
240
174
15
digital input 16
240
175
16
digital input 17
240
176
17
digital input 18
240
177
18
Page:
Device:
Document:
Code:
Date:
18
User manual LS3MUE01