9. HYDRAULIC INSTALLATION
INSTALLER
9.1. General rules for hydraulic installation
The hydraulic connection depends on the type of system.
However, there are some “common rules”:
The hydraulic system must work with pressure.
The system must work with a pressure between 1 and 1.5-2 bar when hot on a closed tank circuit.
DO NOT install the product on a primary system with an open expansion tank.
The presence of a buffer tank (inertial storage tank) is advisable but not mandatory. Its presence has the advantage
of f
reeing the product from the “sudden” demands of the system and allowing integration with other heat sources. It
reduces consumption and increases the efficiency of the system. Edilkamin recommends a 15-20 l/kW buffer tank.
The return temperature of the water to the product must be at least 50-55° C to avoid condensation phenomena.
For the heating of any low temperature radiant panels, a buffer tank (inertial storage tank) must be installed as
indicated by the manufacturer of the radiant panels themselves.
The material used in the circuit must be suitable to withstand any overtemperatures.
The installer must decide whether conditioning products are required based on the type of water and system. In Italy,
refer to Standard UNI 8065 (water treatment in heating systems for civil use).
Direct connection to the radiators, due to the small diameter of their pipes, prevents regular
operation
The hydraulic system must be designed in accordance with local and national regulations.
Installation must be carried out by qualified personnel in accordance with local and national
regulations
NEVER OPERATE THE PRODUCT WITHOUT WATER INSIDE. There is a risk of irreversible
damage to the product
The safety valve outlet must be connected to a collection funnel to channel any discharge in
case of intervention.
Neither the manufacturer nor the retailer is responsible for any flooding caused by incorrect
installations.
The presence of the expansion tank in the product does not guarantee adequate protection
against the thermal expansion suffered by the water in the entire system. The design must
take into account the calculation of the required expansion tank volume
Содержание 812740-1139210
Страница 1: ...TERA H 25 TERA H 30 For all updates visit www edilkamin com MANUAL installation use and maintenance...
Страница 16: ...16 6 4 ECODESIGN technical data Tera H 25...
Страница 17: ...17...
Страница 18: ...18 6 5 ECODESIGN technical data Tera H 30...
Страница 19: ...19...
Страница 22: ...22 1 Open the pellet lid 2 Unscrew the screws 3 Remove the sides 4 Unscrew the fixing screws to the pallet...
Страница 33: ...33 Possible adjustments 10 Assemble the top with the ceramic 11 Tighten the screws...
Страница 34: ...34 12 Open the door 13 Open the lower lid 14 Remove the lower lid...
Страница 36: ...36 10 1 1 Possible adjustments...
Страница 37: ...37 10 1 2 Possible adjustments of pellet lid Possible adjustments Incorrect assembly Correct assembly...
Страница 49: ...49 14 6 Ventilation if present Adjusting ventilation...
Страница 54: ...54 14 9 4 Chrono prog To set the Chrono prog function...
Страница 55: ...55 14 9 5 Chrono temp T1 T2 To set the target temperatures of the Chrono prog...
Страница 56: ...56 14 9 6 Date and time To set the correct date and time...
Страница 57: ...57 14 9 7 Language To select the display language...
Страница 58: ...58 14 9 8 Display To adjust the brightness of the display background...
Страница 61: ...61 14 9 10 Software These readings should only be done when requested by the technician...
Страница 64: ...64 14 9 14 Pellet sensor To turn the pellet level sensor ON or OFF...
Страница 66: ...66 14 9 16 airKare if present To activate or deactivate Airkare mode where present...
Страница 72: ...72 If not performed correctly the operation of the product may be compromised...
Страница 79: ...79...