CMUip-2212 Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 9 

The Field Output Check function is enabled for each channel input individually and provides 

two modes of operation, Field Check Mode and Field Check Status. 

2.13.1 FIELD CHECK MODE 

The CMUip-2212 will compare the active states of the field signals with the states reported 

by the ATC in the Type 81 (67) frame. When a mismatch is detected for less than the No 

Fault time  (section  5.2)  the  CMUip-2212  will not cause a LFSA.  When a mismatch is 

detected for greater than the Fault time (section 5.2), the CMUip-2212 will cause a LFSA.   
The Field Check Mode is typically caused by a miss-wired or improperly configured cabinet. 

When the Field Check Mode is detected the FIELD CHECK front panel indicator will be 

illuminated solid. 
Field Output Check monitoring will be disabled when the  MC COIL STATUS input is not 

active.  There is programming in the Datakey to disable Field Output Check monitoring on a 

channel input basis. 

2.13.2 FIELD CHECK STATUS 

The CMUip-2212 will compare the active states of the field signals with the states reported 

by the CU in the Type 81 (67) frame. When a mismatch is detected while a Conflict, Lack of 

Signal, or Multiple fault is timing, Field Check Status will be reported with the fault to 

indicate the faulty channel(s) and color(s). 
If a Conflict, Lack of Signal, or Multiple fault has triggered the CMUip-2212  to the fault 

mode and the CMUip-2212 indicates that there is no Field Check Status, the ATC or ATC 

programming is the most likely cause. The lack of Field Check Status indicates the ATC 

drove the signals to an improper state. If a Conflict, Lack of Signal, or Multiple fault has 

triggered the CMUip-2212  to the fault mode and the CMUip-2212  indicates that there is 

Field Check Status, then cause of the malfunction can be isolated to the SIU, load switch, 

field wiring, or signal load. 
When Field Check Status is detected the FIELD CHECK front panel indicator will be flash 

at a 2Hz rate. 
Field Output Check monitoring will be disabled when the  MC COIL STATUS input is not 

active.  There is programming in the Datakey to disable Field Output Check monitoring on a 

channel input basis. 

2.14 DIAGNOSTIC ERROR 

The  CMUip-2212  is provided with a resident series of self-check diagnostic capabilities. 

When a Diagnostic fault is detected, a LFSA-R will be set and the DIAGNOSTIC indicator 

illuminated. Should a Diagnostic error occur, other fault indicators that may be concurrently 

displayed with the DIAGNOSTIC indicator may not be valid due to the nature of these 

hardware and/or firmware failures. 

2.14.1 RAM MEMORY DIAGNOSTIC 

This test will verify that all RAM elements are operating correctly at power-up or following a 

Unit Reset. 

2.14.2 NONVOLATILE MEMORY DIAGNOSTIC 

This test will verify that the nonvolatile flash ROM and event log eeprom contain the proper 

data. The routine will perform a check on each ROM device and make a comparison with a 

check value.  

Содержание CMUip-2212 Series

Страница 1: ...TOR UNIT Firmware Version 2 0 vXX20 Issue J PCB REVISION MAY 2019 pn 888 2212 001 CMUip 2212 ATCC Cabinet Monitor Unit Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4 5 OR HIGHE...

Страница 2: ...ETARY TECHNICAL INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2019 EDI U S Pat No 7 246 037 Can...

Страница 3: ...ance Monitor 6 2 8 Yellow Plus Red Clearance Monitor 7 2 9 Local Flash Status 7 2 9 1 Local Flash Status Recovery 7 2 10 Circuit Breaker Trip Status 7 2 11 Flasher Unit Output Failed Alarm 7 2 12 CMU...

Страница 4: ...s 1 Address Inputs 16 3 7 Serial Bus 1 Disable input 17 3 8 CMUip 2212 Temperature 17 Section 4 FRONT PANEL DESCRIPTION 18 4 1 Indicators 18 4 1 1 Power Indicator 18 4 1 2 48VDC FAIL Indicator 18 4 1...

Страница 5: ...6 1 1 CMUip 2212 HV CMUip 2212 VHV Pin List 25 6 1 2 CMUip 2212 LV Pin List 25 6 2 CMUip 2212 Ethernet LAN Port 26 6 2 1 Ethernet LAN Cable 26...

Страница 6: ...roper operation of the cabinet equipment as well as providing important diagnostic functions used for trouble shooting malfunctioning equipment 1 2 CHANNEL CONFIGURATION The CMUip 2212 can be configur...

Страница 7: ...CMUip 2212 provides limited operational status Detailed status is obtained through the front panel Ethernet port CMUip 2212 using Eberle Design ECcom Signal Monitor Communications software running on...

Страница 8: ...is data allows the CMUip 2212 to better respond to and diagnose fault situations 1 7 1 SERIAL BUS 1 MESSAGE TYPES The CMUip 2212 is compatible with the following message types Type 60 Module Identific...

Страница 9: ...Reset Button or EXTERNAL RESET TEST input or a CMUip 2212 Power Fail will reset a LATCHED RESETTABLE FAILED STATE ACTION LFSA R A NONLATCHED FAILED STATE ACTION NFSA will be reset if the fault condit...

Страница 10: ...ause a LFSA 2 3 SERIAL BUS MONITOR The CMUip 2212 communicates with both Serial Bus SB 1 and 3 In SB 1 the CMUip 2212 is a Secondary device polled by the ATC Primary device On SB 1 the CMUip 2212 will...

Страница 11: ...5 and 16 when Virtual channels are used Lack of Signal Input monitoring will be disabled for all channels when the MC COIL STATUS input is not active There is programming in the Datakey to disable Lac...

Страница 12: ...y Unit ADU will display the active field signals This can be helpful to verify that flash mode is active on all outputs appropriately Note that a short time delay will be introduced to the ADU display...

Страница 13: ...e high the CMUip 2212 will begin timing the programmed Minimum Flash Interval During the Minimum Flash Interval the CMUip 2212 will be in NFSA 2 12 4 POWER UP Following initial application of MAINS vo...

Страница 14: ...triggered the CMUip 2212 to the fault mode and the CMUip 2212 indicates that there is no Field Check Status the ATC or ATC programming is the most likely cause The lack of Field Check Status indicate...

Страница 15: ...or pulsing in nature The RMS signal detection algorithm is designed to filter out short term transients commonly found on the electrical service and provide noise immunity against false signal detect...

Страница 16: ...PROTECTED TURN CHANNEL The Protected Turn Channel of the FYA channel pair is composed of the solid Green arrow Ga indication of the FYA Signal Output Group 2 16 1 2 PERMISSIVE TURN CHANNEL The Permiss...

Страница 17: ...ogramming of the Protected Turn channel Green arrow of the pair 2 16 2 1 2 PERMISSIVE YELLOW CHANGE INTERVAL CONFLICT During the Yellow change interval of the Permissive Turn channel flashing Yellow a...

Страница 18: ...rmissive flashing Yellow arrow This allows the CU to sequence from the Permissive Left turn channel directly to the Protected Left Turn channel without a solid Yellow arrow clearance interval 2 16 3 R...

Страница 19: ...ough channel is still showing a green ball When the FYA Yellow Trap Conflict condition is detected the CMUip 2212 will enter the fault mode transfer the OUTPUT relay contacts to the Fault position and...

Страница 20: ...ill be sensed active when the load current exceeds the programmed Channel LOS Current Sense Threshold programmed for that channel in the Datakey A channel will not be sensed active when the load curre...

Страница 21: ...be considered active see Section 5 1 when the door is open These inputs will not be considered active when the door is closed The CMUip 2212 will report the state of these inputs in the Type 209 195 f...

Страница 22: ...When the SERIAL BUS 1 DISABLE input is connected to VDC GROUND True The CMUip 2212 will not communicate on Serial Bus 1 or set a FSA condition if communications from the ATC is not present See sectio...

Страница 23: ...d The 48VDC 24VDC FAIL and 12VDC FAIL will pulse when either the POWERDOWN or NRESET input is False low See section 2 12 2 4 1 4 12VDC FAIL INDICATOR A red 12VDC FAIL indicator will illuminate when th...

Страница 24: ...ator will illuminate when the CMUip 2212 is in FSA as a result of a Serial Bus 3 fault See section 2 3 2 4 1 14 DIAGNOSTIC INDICATOR A red DIAGNOSTIC indicator will illuminate when the CMUip 2212 is i...

Страница 25: ...power is applied to the CMU 2212 the CMUip 2212 will continue to use the parameters from the removed Datakey until Reset is applied a new Datakey is installed or a power up cycle occurs If a CMUip 22...

Страница 26: ...ss than 77 Vrms DC Control Monitors Local Flash Status MC Coil Status FTR Coil Drive CB Trip Status Active greater than 44 Vdc Not Active less than 42 Vdc Front Rear Door Switch Active greater than 13...

Страница 27: ...than 11 Vdc Power Fail Monitor Mains Restore greater than 45 1 Vrms Mains Dropout less than 43 1 Vrms DC Voltage Monitors 48 Volt Monitor Active greater than 46 Vdc Not Active less than 44 Vdc 24 Vol...

Страница 28: ...han 164 2 Vrms DC Voltage Monitors 24 Volt Monitor Active greater than 22 Vdc Not Active less than 18 Vdc 12 Volt Monitor Active greater than 11 Vdc Not Active less than 9 Vdc Logic Inputs External Te...

Страница 29: ...200 ms Typical 300 ms Circuit Breaker Trip Fault greater than 400 ms No Fault less than 200 ms Typical 350 ms AC Line Level Sense Fault greater than 750 ms No Fault less than 550 ms Typical 650 ms Fla...

Страница 30: ...c A16 Nreset B16 Nreset A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output R...

Страница 31: ...Rear B28 Reserved A29 Reserved B29 DC MAINS Power A30 Reserved B30 No Connect A31 Equipment Ground B31 Reserved A32 Reserved B32 MAINS Ground Note Output Relay NO is open during FSA de energized 6 2...

Отзывы: