6 Troubleshooting 

Problem 

Possible Cause 

Solution 

Unit does not turn on. 

Wall plug is disconnected.  

Insert plug firmly into proper wall outlet. 

House fuse blown or circuit breaker 
tripped.  

Replace fuse with time delay type or reset circuit 
breaker. 

Power cord is tripped.  

Press the RESET button on the power cord.  If power 
cord is damaged replace power cord. 

Unit is turned OFF. 

Turn unit ON and set to desired setting. 

Ribbon cable to control panel is 
disconnected. 

Remove outer shell and reconnect cable. 

Loose or disconnected wiring on 
main PCB. 

Remove outer shell. Check all connections to the 
PCB and reconnect any loose or disconnected leads. 

Condensate water tray is full and/or 
water light is on. 

Drain condensate water.  Make sure water level 
switch is 

operating correctly and not stuck in “full” 

position or being interfered with. 

Unit does not blow 
cold air. 

Room temperature is below 
61ºF(16ºC.) 

Cooling will not occur until room temperature rises 
above 61ºF(16ºC.)  

Unit is not in cooling mode. 

Set the unit to cooling mode 

– blue light is on. 

Set temperature is too high. 

Set to a Lower temperature. 

Air filter is dirty. 

Clean filter. 

Exhaust air duct is installed 
incorrectly or blocked. 

Connect exhaust duct so if functions correctly.  Clear 
blockage. 

Refrigerant leak. 

Find leak and repair.  Recharge with refrigerant. 

Evaporator is frosted. 

The unit needs to defrost and will resume normal 
operation after it is finished. 

Unit blows cold air 
but does not lower 
room temperature. 

Fan speed is set too low.  

Increase fan speed to improve air flow. 

Exhaust air duct is not installed, is 
installed incorrectly or blocked.   

Connect exhaust duct so if functions correctly.  Clear 
blockage. 

Room area is too large. 

Reduce room size, add another unit or larger unit. 

Open windows or doors. 

Close all open windows and doors. 

Ambient temperature is too high. 

The unit may not work if the room temperature is 
above 90°F. 

Room has too many heat sources. 

Remove or shut off additional heat sources. Close 
curtains or blinds to minimize the amount of direct 
sunlight entering the room.  

Содержание AP8000W

Страница 1: ...ranty service should be performed by an authorized service representative only SERVICE MANUAL EdgeStar Small Room Portable Air Conditioner with 71 Pint Dehumidifier MODEL AP8000W Document Type Service...

Страница 2: ...terpretation or misuse of the information provided nor does it assume any liability in connection with its use The safeguards and warnings indicated in this manual do not cover all possible conditions...

Страница 3: ...iance is properly grounded Do not bypass cut or remove the grounding plug If the power cord is damaged it must be replaced by the manufacturer or a qualified technician Do not use extension cords or p...

Страница 4: ...exposed to the weather Disconnect from the power socket before cleaning or maintenance If the plug power cord is damaged it must be replaced by the manufacturer or an authorized service representative...

Страница 5: ...ower 860 W Current 7 9 A Cooling Capacity SACC 4500 BTU Cooling Capacity ASHRAE 8000 BTU Color White Dehumidifying Capacity 71 pints Day Coolant R 410A Timer 24 Hour Dimensions W x H x D 19 25 x 24 75...

Страница 6: ...5 2 Exploded View and Parts List...

Страница 7: ...INTAKE GRILLE 15 EVAPORATOR 48 INTAKE GRILLE 16 DISCHARGE PIPE 49 COVER 17 SUCTION PIPE 50 FIXTURE 18 CAPILARY TUBE 51 COVER 19 FILTER DRYER 52 BRACKET 20 FAN HOUSING 53 PLUG 21 FAN HOUSING 54 SENSOR...

Страница 8: ...7 3 Wiring Diagram 4 Refrigerant System Diagram...

Страница 9: ...rms to the chart below When TA TS for 1 minute the compressor turns off When TA TS 2 the compressor turns on 5 3 Fan Only Mode Green Light If the temperature can t be controlled by the selected mode a...

Страница 10: ...in Dehumidifying mode you must manually drain the water from the unit Additionally the ambient temperature in the room will probably rise by a few degrees if you do not use the exhaust hose You will b...

Страница 11: ...l room temperature rises above 61 F 16 C Unit is not in cooling mode Set the unit to cooling mode blue light is on Set temperature is too high Set to a Lower temperature Air filter is dirty Clean filt...

Страница 12: ...Attach the drain plug Base plate is cracked Replace base plate Sounds or vibration When unit is turned on or off the outer shell pops or clicks Normal sound Outer shell is contracting or expanding an...

Страница 13: ...l St Suite 1800 Austin TX 78754 support edgestar com service edgestar com edgestar com Warranty service should be performed by an authorized service representative only DATE REVISION NOTES 04 11 2018...

Отзывы: