13
4.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5.
Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
6.
After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas-burning appliance to their previous
conditions of use.
7.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
When re-sizing any portion of the common venting
system, the common venting system should be resized
to approach the minimum size as determined using the
appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
Vent connectors serving appliances vented by natural draft shall
not be connected into any portion of mechanical draft systems
operating under positive pressure.
CHIMNEY AND VENT PIPE CONNECTION
Figure 7 - Typical Masonry Chimney Requirements
P/N 1305004, Rev. E [8/31/2016]
Содержание PENNCO 16 Series
Страница 30: ...30 REPAIR PARTS P N 1305004 Rev E 8 31 2016 ...
Страница 31: ...31 REPAIR PARTS P N 1305004 Rev E 8 31 2016 ...
Страница 34: ...34 NOTES P N 1305004 Rev E 8 31 2016 ...
Страница 35: ...35 Date Service Performed Company Name Tech Initials Company Address Phone P N 1305004 Rev E 8 31 2016 ...
Страница 36: ...PENNCO BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...