TABLE 1: SEA LEVEL RATINGS - NATURAL AND PROPANE GASES
Input (MBH)
(1)
Heating Capacity
(MBH)
(1)(2)
Net AHRI Rating
(MBH)
(1)
AFUE
(2)
Flue Diameter
Shipping Wt.
High Fire
200
182
158
92.5%
2” CPVC & 3” PVC
284 lbs.
Low Fire
80
73
63
(1)
1 MBH = 1,000 BTUH (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Effi ciency) are based on DOE (Department of Energy) test procedures.
TABLE 2: 95M-200 HIGH ALTITUDE DERATE CHART
Input
(MBH)
Altitude (In Feet)
3,000
(2)
4,000
(2)
5,000
(3)
6,000 7,000 8,000
9,000
10,000
High Fire
196
192
177
174.5
172
169
168
167
Low Fire
78.4
76.8
115
113.5
112
110
109
108
1)
Boiler Input Rate is determined at minimum vent length. The rate will decrease as vent length increases.
2)
Parameter 17 is set to 2,250 at elevations of 2,000 feet and below.
3)
Parameter 17 must be raised to 3,200 at altitudes or elevations of 2,000 feet and above.
• Heating Capacity indicates amount of heat available after subtracting losses up the stack. Most of this heat is available
to heat water. Small portion is heat loss from jacket and boiler surfaces, and it is assumed this heat stays in the
structure.
• Net AHRI Rating represents portion of remaining heat that can be applied to heat radiation or terminal units (i.e.,
fi nned tube baseboard, cast iron radiators, radiant fl oor, etc.) Difference between Heating Capacity and Net AHRI
Rating, called piping and pickup allowance, establishes reserve for heating volume of water in the system and
offsetting heat losses from piping.
• Net AHRI Ratings shown are based on piping and pickup factor of 1.15 in accordance with AHRI Standard. Net AHRI
Rating of selected boiler should be greater than or equal to calculated peak heating load (heat loss) for building or
area(s) served by boiler and associated hot water heating systems. Consult manufacturer before selecting boiler for
installations having unusual piping and pickup requirements.
4 - BOILER RATINGS & CAPACITIES
5
Содержание Olsen OQ95M-200
Страница 2: ...1 DIMENSIONS OPENING FOR SAFETY RELIEF VALVE DISCHARGE PIPE 30 785mm 39 1 1m 18 458mm 2 ...
Страница 27: ...APPENDIX A BOILER PIPING AND WIRING Electrical Wiring Diagram 27 ...
Страница 49: ...49 NOTES ...
Страница 50: ...50 NOTES ...
Страница 51: ...51 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD ...
Страница 52: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...